Phoenix PSR-SCP- 24DC/ESD/4X1/30-safety relay 2981800, safety relay, used for emergency stop and safety door monitoring, safety level up to SIL 3 or EN ISO 13849 standard Cat. 4, PL e, automatic or manual activation, 2 normally open contacts with 0.1 s to 30 s shutdown delay, plug-in screw terminal

Application Description
Application Description for industrial applications only

Product Type safety relay
product series PSRclassic
Application Emergency stop button
safety door
grating
kit includes 1217839 PSR-SCP-24DC/ESD/4X1/30-SET35
control Single and Dual Channel
mechanical life about 107Switch Times
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
Typical Response Time 150 ms (can be monitored/manual and automatic reset)
Typical Release Time 20 ms (no delay contact)
100 ms (delay contact)
Delay Time Range 0.1 s ... 30 s ± 30% (settable)
Recovery Time 330 ms (restart)
1 s (electrical torque)

rated conditions 1.8W
Rated operating mode 100% Eligible
Electrical clearance and creepage distance between power supply circuits
Rated insulation voltage 250V
rated overvoltage/insulation 4 kV/foundation isolation withstand voltage
Power
Rated control circuit supply voltage US 24V DC
Impulse current Typical 250 mA

Overview
Rated input voltage UN 24V DC
to UNas reference 0.85 ... 1.1
UN 75 mA DC
input/start and feedback circuit voltage approx. 24V DC
Typical Response Time 150 ms (can be monitored/manual and automatic reset)
Typical Release Time 20 ms (no delay contact)
100 ms (delay contact)
Typical Release Time Range 0.1 s ... 30 s
Recovery Time 330 ms (restart)
1 s (electrical torque)
protection circuit Suppressor Diode, 33V DC
Allowable Total Conductor Resistance 500 Ω (UN)
Operating voltage display Green LED
Status Display LED K1/K2 and K3(t)/K4(t), green

Contact Type 4 normally open safety contact outputs
Contact Material AgSnO2
maximum switching voltage 250V AC/DC
Minimum Switching Voltage 15V AC/DC
limit continuous current 6 A (N/O contact)
Maximum starting current 6 A
Minimum impulse current 25 mA
the square of the total current value 120 A2(see Attenuation curve)
Maximum power rating (resistive load) 144W (24VDC,t=0ms)
288W (48VDC,t=0ms)
90W (110VDC,t=0ms)
88W (220VDC,t=0ms)
1500 VA (250V AC,τ = 0 ms)
Maximum power rating (inductive load) 42W (24V DC, τ = 40 ms)
33W (48V DC,τ = 40 ms)
25W (110V DC,τ=40ms)
23W (220V DC,τ=40ms)
Minimum on-off capacity 0.4W
On-off capacity (360/h cycle) according to customer requirements
On-off capacity (3600/h cycle) 3 A (24V (DC13))
3 A (230V (AC15))
output fuse 10 A gL/gG NEOZED (N/O contact)

Phoenix PSR-SCP- 24DC/ESD/4X1/30-Safety Relay 2981800