Phoenix QUINT-PS/3AC/24DC/40-power supply 2866802, primary switching power supply QUINT POWER, screw connection, DIN rail installation, SFB Technology (Selective Fuse Breaking), input: 3 phases, output: 24V DC/40 A

AC operation
Rated input voltage range 3x 400V AC ... 500V AC
Input Voltage Range 3x 400V AC ... 500V AC -20 % ... +15%
Supply Voltage AC/DC
Impulse current < 15 A (at 25°C)
impulse current integral (I2t) < 1 A2s
Surge current limit 15 A
AC frequency range 45Hz ... 65Hz
DC frequency range 0Hz
grid buffer time > 25 ms (400V AC)
> 35 ms (500V AC)
power consumption 3x 2.1 A (400V AC)
3x 1.7 A (500V AC)
Rated power consumption 1342 VA
protection circuit transient surge protection; varistor, gas discharge tube
power factor (cos phi) 0.76
Typical Response Time < 0.5 s
Allowable Spare Fuses B6 B10 B16 AC:
Allowed DC Spare Fuses DC: Connect a suitable fuse
recommend use 6 A ... 20 A (characteristics B, C, D, K or similar)
PE discharge current < 3.5 mA
DC operation
Rated input voltage range 500V DC ... 600V DC
Input Voltage Range 500V DC ... 600V DC -10 % ... +33 % (mid-point earthed)
power consumption 2.2 A (500V DC)
1.9 A (600V DC)
recommend use 1x 6 A ≥ 1000V DC (10 x 38 mm, 30 kA L/R = 2 ms)

efficiency 94% typical (400V AC)
output characteristics U/ I
Rated output voltage 24V DC ±1%
output voltage (USet) setting range 18V DC ... 29.5V DC (> 24V DC, stable capacity limit)
Rated output current (IN) 40 A
POWER BOOST (IBoost) 45 A (-25°C ... 40°C constant, UOUT= 24V DC)
Static Boost (IStat.Boost) 45 A
selective fusing (ISFB) 215 A (12 ms)
Type of thermal magnetic circuit breaker B2 / B4 / B6 / B10 / B16 / B25 / C2 / C4 / C6 / C13
Attenuation 60°C ... 70°C (2.5 %/K)
feedback voltage resistance ≤ 35V DC
output ≤ 35V DC
control deviation <1% (load change, static 10%... 90%)
<3% (load change, dynamic 10%... 90%)
< 0.1 % (input voltage variation is ± 10 %)
residual wave < 40 mVSS(rated value)
Short-circuit protection is
output power 960W
1080W
peak switching voltage rated load < 5 mVSS(rated, 20MHz)
maximum no-load power consumption 18W
Maximum rated load power loss 63W
rise time < 0.15 s (UOUT(10%... 90%))
and connect Yes, for redundancy and increased capacity
Concatenation is
signal: DC OK active
Output Description UOUT>0.9xUN: High Signal
Switching voltage range 18V DC ... 24V DC
output voltage +24V DC
Maximum starting current ≤ 20 mA (short-circuit protection)
Continuous load current ≤ 20 mA
signal: DC OK floating point
Output Description relay contacts, UOUT>0.9xUN: contact attraction
maximum switching voltage 30V AC/DC
24V DC
Maximum starting current 0.5 A
1 A
Continuous load current ≤ 1 A
signal: POWER BOOST, active
Output Description IOUTN: High signal
Switching voltage range 18V DC ... 24V DC
output voltage +24V DC
Maximum starting current ≤ 20 mA (short-circuit protection)
Continuous load current ≤ 20 mA

Phoenix QUINT-PS/3AC/24DC/40-Power 2866802

Created on:2025-02-11 15:31

News Dynamics

NEWS