| Use Restrictions | |
| EMC Description | EMC: Class A products, see the manufacturer's declaration in the download area |
| Product Type | Feeder Isolator |
| product series | MINI Analog Pro |
| Channels | 1 |
| Model | isolation amplifier |
| insulation characteristics: GB Standard | |
| Overvoltage Category | II |
| pollution level | 2 |
| electrical isolation | 3 End Isolation |
| galvanic isolation between input and output | is |
| cut-off frequency (3dB) | > 1.75 kHz |
| protection circuit | transient protection |
| Signal Transmission Behavior | In = Out |
| step response (10-90%) | < 200 & micro;s (typical) |
| maximum temperature coefficient | 0.0075 %/K |
| temperature coefficient, typical | 0.0075 %/K |
| Maximum transmission error | 0.05 % (final value in repeater power supply operation) |
| 0.1 % (final value in isolator operation) | |
| Electrical isolation input/output/power supply | |
| Rated insulation voltage | 300Vrms |
| Test Voltage | 3 kV AC (50 Hz, 60 s) |
| insulation | reinforced insulation conforming to IEC/EN 61010-1 |
| power supply | |
| Rated supply voltage | 24V DC |
| Supply Voltage Range | 9.6V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard)) |
| Typical current consumption | 25 mA (24VDC, isolator operation) |
| 50 mA (24VDC, feeder isolator operation) | |
| 55 mA (12VDC, isolator operation) | |
| 110 mA (12VDC, feeder isolator operation) | |
| power consumption | ≤ 1400 mW (IOUT= 20 mA,9.6V DC,600 Ω load) |
| signals: current | |
| Input Description | sensor circuit |
| Input Number | 1 |
| current input signal | 0 mA ... 20 mA (Isolator operation) |
| 4 mA ... 20 mA (feeder isolator and isolator operation) | |
| input current | (+0.7V for testing diodes) |
| Transmitter supply voltage | > 19.5V |
| signals: current | |
| outputs | 1 |
| No-load voltage | < 20V |
| current output signal | 0 mA ... 20 mA (Isolator operation) |
| 4 mA ... 20 mA (feeder isolator and isolator operation) | |
| Maximum current output signal | 24 mA |
| load/output load current output | ≤ 600 Ω (20 mA) |
| fluctuation | < 20 mVSS(600 Ω) |
| Connection Mode | screw connection |
| stripping length | 10mm |
| thread | M3 |
| Rigid conductor cross section | 0.2 mm² ... 1.5 mm² (with cold press head) |
| 0.14 mm² ... 2.5 mm² (without cold head) | |
| Flexible Wire Cross Section | 0.14 mm² ... 2.5 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 (flexible) |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Explosion-proof installation (EPL) | Gc |
| Div. 2 |
| Data Communication (Bypass) | |
| HART function | is |
| cut-off frequency (3dB) | 1.75 kHz |
| Status Display | Green LED (supply voltage) |
Phoenix MINI MCR-2-RPSS-I-I-Feed Isolator 2902014