Phoenix MACX MCR-UI-UI-UP-NC-isolation amplifier 2811297, isolation amplifier, with safe electrical isolation and wide-area power input (24V ... 230V AC/DC). Front DIP switch; more than 1600 signal conversion functions can be set. Standard configuration (IN 0 ... 10V/OUT 0 ... 20 mA), screw wiring, SIL.
| Product Type | isolation amplifier |
| Product Series | MACX Analog |
| Channels | 1 |
| Model | Isolation Amplifier with SIL Functional Safety |
| configuration | DIP switch |
| Span adjustment | ± 4% |
| Zeroing | ± 4% |
| galvanic isolation between input and output | is |
| cut-off frequency (3dB) | 10 kHz (switchable to 30Hz) |
| rated conditions | < 0.9W (20 mA) |
| protection circuit | transient protection |
| step response (10-90%) | 35 µs (10 kHz) |
| 11 ms (30 Hz) | |
| maximum temperature coefficient | 0.0075 %/K |
| Maximum transmission error | ≤ 0.1 % (compare final value) |
| electrical isolation | |
| Test Voltage | 2.5 kV AC (50 Hz, 60 s) |
| Overvoltage Category | II |
| pollution level | 2 |
| Electrically isolated input/output/power supply IEC/EN 61010-1 | |
| Standards/Regulations | IEC/EN 61010-1 |
| Rated insulation voltage | 300Vrms |
| insulation | security isolation |
| galvanically isolated input/output/power supply IEC/EN 60079-7 | |
| Standards/Regulations | IEC/EN 60079-7 |
| Rated insulation voltage | 275V |
| power supply | |
| Rated supply voltage range | 24V AC/DC ... 230V AC/DC -20 % ... +10 % (50/60 Hz) |
| Supply Voltage Range | 19.2V AC/DC ... 253V AC/DC (50/60 Hz) |
| power consumption | < 0.8W (24V DC/20 mA) |
| < 0.9W (230V AC/20 mA) | |
| signal: current/voltage | |
| Number of inputs | 1 |
| voltage input signal | 0 mV ... 50 mV |
| 0 mV ... 60 mV | |
| 0 mV ... 75 mV | |
| 0 mV ... 100 mV | |
| 0 mV ... 120 mV | |
| 0 mV ... 150 mV | |
| 0 mV ... 200 mV | |
| 0 mV ... 300 mV | |
| 0 mV ... 500 mV | |
| 0V ... 1V | |
| 0V ... 1.5V | |
| 0V ... 2V | |
| 0V ... 3V | |
| 0V ... 5V | |
| 0V ... 10V (can be configured with DIP switches) | |
| 0V ... 15V | |
| 0V ... 20V | |
| 0V ... 30V | |
| 0V ... 50V | |
| 0V ... 100V | |
| -50 mV ... 50 mV | |
| -60 mV ... 60 mV | |
| -75 mV ... 75 mV | |
| -100 mV ... 100 mV | |
| -120 mV ... 120 mV | |
| -150 mV ... 150 mV | |
| -200 mV ... 200 mV | |
| -300 mV ... 300 mV | |
| -500 mV ... 500 mV | |
| -1V ... 1V | |
| -1.5V ... 1.5V | |
| -2V ... 2V | |
| -3V ... 3V | |
| -5V ... 5V | |
| -10V ... 10V | |
| -15V ... 15V | |
| -20V ... 20V | |
| -30V ... 30V | |
| -50V ... 50V | |
| -100V ... 100V | |
| 1V ... 5V | |
| 2V ... 10V | |
| minimum voltage input signal | ± 50 mV |
| Maximum voltage input signal | ± 100V |
| current input signal | 0 mA ... 1 mA (configurable with DIP switch) |
| 0 mA ... 1.5 mA | |
| 0 mA ... 2 mA | |
| 0 mA ... 3 mA | |
| 0 mA ... 5 mA | |
| 0 mA ... 10 mA | |
| 0 mA ... 15 mA | |
| 0 mA ... 20 mA | |
| 0 mA ... 30 mA | |
| 0 mA ... 50 mA | |
| 0 mA ... 100 mA | |
| -1 mA ... 1 mA | |
| -1.5 mA ... 1.5 mA | |
| -2 mA ... 2 mA | |
| -3 mA ... 3 mA | |
| -5 mA ... 5 mA | |
| -10 mA ... 10 mA | |
| -15 mA ... 15 mA | |
| -20 mA ... 20 mA | |
| -30 mA ... 30 mA | |
| -50 mA ... 50 mA | |
| -100 mA ... 100 mA | |
| 1 mA ... 5 mA | |
| 2 mA ... 10 mA | |
| 4 mA ... 20 mA | |
| minimum current input signal | ± 1 mA |
| Maximum current input signal | ± 100 mA |
| input voltage | approx. 1 MΩ (± 1V DC ... ± 100V DC) |
| input current | approx. 10 Ω (± 10 mA DC ... ± 100 mA DC) |
Phoenix MACX MCR-UI-UI-UP-NC-Isolation Amplifier 2811297