Phoenix VAL-MS-T1/T2 1000DC-PV/2V-1/2 category lightning protection/surge protector 2801160, lightning protection device/surge protector, used for 2-position insulated grounding 1,000V DC photovoltaic voltage system, suitable for DIN Rail installation, 3-position base element, three pluggable temperature monitoring protection elements, each plug has status information.

Product Type PV Protector
product series VALVETRAB MS
IEC Category PV I / II
PV T1 / T2
EN Type T1 / T2
IEC power supply system DC
type DIN rail module, split, detachable
distance between active and grounded components 8mm
Installation position Indoor
separation device inside
accessibility accessible
Connection Configuration Y Configuration
SPD failure behavior OCFM (Partition Error Behavior)
Surge protection fault alarm with visual status indication window
insulation characteristics
Overvoltage Category III
pollution level 2

Connection Mode screw connection
thread M5
Tightening torque 3 Nm (1.5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
stripping length 16mm
Flexible Wire Cross Section 1.5 mm² ... 25 mm²
Rigid conductor cross section 1.5 mm² ... 35 mm²
Connectable Guide Cross Section AWG 15 ... 2
Connection Mode fork cable end
Flexible Wire Cross Section 1.5 mm² ... 16 mm²

Dimensional drawing
width 53.4mm
height 89.8mm
depth 65.7mm (7.5mm with DIN rail)
Horizontal stitch pitch 3 Division

color black (RAL 9005)
flame retardant rating to UL 94 V-0
material 600
insulation material PA 6.6-FR
PBT-FR
Material Group I
Shell Material PA 6.6-FR
PBT-FR

Mechanical parameters
Open Side Panel No

protection channel (L ) - (L-)
(L ) - PE
(L-) - PE
Direction of action (L )-PE & (L-)-PE & (L )-(L-)
Rated load current IL 80 A
Residual Flow IPE ≤ 20 µA DC
≤ 350 µA AC
Standby power consumption PC ≤ 25 mVA
Nominal discharge current In(8/20)µs 15 kA
Maximum discharge current Imax(8/20) µs 40 kA
impulse discharge current (10/350)& micro;s, charging 2.5
impulse discharge current (10/350)& micro;s, specific energy 6.25 kJ/Ω
impulse discharge current (10/350)& micro;s, peak limp 5 kA
Total discharge current Itotal(8/20) µs 40 kA
Total discharge current Itotal(10/350) µs 5 kA
voltage protection level Up ≤ 3.5 kV
Residual pressure Ures ≤ 3.5 kV (In)
≤ 2.9 kV (at 5 kA)
≤ 3.2 kV (10 kA)
≤ 3.7 kV (20 kA)
≤ 4.1 kV (at 30 kA)
≤ 4.6 kV (at 40 kA)
response time tA ≤ 25 ns

Phoenix VAL-MS-T1/T2 1000DC-PV/2V-1/2 category lightning protection/surge protector 2801160

Created on:2025-02-17 15:29