Phoenix IB IL 24 LPSDO 8 V2-PAC-safety module 2700606, safety-related digital output module, IP20 protection level, used in SafetyBridge systems. The module has 4 safe digital outputs for 2 channels, or 8 safe digital outputs for 1 channel

width 48.8mm
height 119.8mm
depth 71.5mm
Notes on dimensional data Shell Size

Application Description
Application Description for industrial applications only

Inline Local Bus
Channels 2
Connection Mode Inline data span block
transmission speed 500 kBit/s / 2 MBit/s (switchable)

SafetyBridge Properties
and I/O module connections max. 5 (Secure Digital I/O Module)
Logical Storage 24 kilobytes kByte
Module
ID Code (dec.) 171
Hex ID Encoding AB
Length Encoding (Hexadecimal) 18
length encoding (decimal) 24
Process Data Channel 48 Byte
Input Address Area 48 Byte ((operation mode: SafetyBridge 24 characters))
Output Address Area 48 Byte ((operation mode: SafetyBridge 24 characters))
Register Length 48 Byte
the required parameter data 1 Byte ((operation mode: SafetyBridge 24 characters))
5 Byte ((operation mode: SafetyBridge 24 characters))

digital quantity:
Output Name Digital Output
Connection Mode pull-back spring connection
connection system 2,3,4 lines
outputs 4 (for dual channel distribution)
8 (for single channel distribution)
8
protection circuit output
output voltage 24V DC (US- 1 V)
output current max. 6 A (total current of all outputs,-25°C ... 50°C)
max. 4 A (total current of all outputs,>-50°C ... 55°C)
Maximum output current per group 3 A
the maximum output current per channel 2 A
Rated output voltage 24V DC
load rating, inductive See Safety Data
rated load, indicator light See Safety Data
Rated load, resistive See Safety Data
Inductor overload action output may be corrupted

Product Type I/O components
product series Inline
Application Functional Safety
SafetyBridge Technology
type Module
diagnostic information Digital output short circuit or overload fault information is displayed in the form of diagnostic codes (bus) via LEDs on the motor

rated conditions 144W
transmission medium copper cable
potential: communication power supply (UL)
supply voltage 7.5V DC (see safety data)
current consumption maximum 230 mA (see safety data)

Phoenix IB IL 24 LPSDO 8 V2-PAC-Safety Module 2700606