Phoenix VAL-MS 580-ST-2 type surge protector 2920434, type 2 surge protection plug, using high-power varistor, used with VAL-MS base, with temperature monitoring and optical fault alarm. Working voltage: 580V AC

Product Type Spare Plug
product series VALVETRAB MS
IEC Category II
T2
EN Type T2
IEC power supply system TN
IT
type needle type
distance between active and grounded components 5mm
Bits 1
Surge protection fault alarm with visual status indication window
insulation characteristics
Overvoltage Category III
pollution level 2

Rated frequency fN 50Hz (60 Hz)

Connection Mode pluggable

Dimensional drawing
width 17.5mm
height 52.4mm
depth 55.3mm
Horizontal stitch pitch 1 Partition

color black (RAL 9005)
flame retardant rating to UL 94 V-0
material 600
insulation material PA 6.6
Material Group I
Shell Material PA 6.6

protection channel L-PE
L-PEN
movement direction 1L-N/PE
Rated voltage UN 400/690V AC (TN)
500V AC (IT)
Rated frequency fN 50Hz (60 Hz)
Maximum continuous voltage Uc 580V AC
Residual Flow IPE ≤ 0.25 mA
Standby power consumption PC ≤ 150 mVA
Nominal discharge current In(8/20)µs 15 kA
Maximum discharge current Imax(8/20) µs 30 kA
Rated short-circuit current ISCCR 25 kA
voltage protection level Up ≤ 2.5 kV
Residual pressure Ures ≤ 2.5 kV (In)
≤ 2.3 kV (10 kA)
≤ 2.1 kV (at 5 kA)
≤ 1.9 kV (at 3 kA)
UT 690V AC (5 seconds/withstand mode)
762V AC (120 min/withstand mode)
response time tA ≤ 25 ns
maximum spare fuse with branch wiring 125 A (gG)

Phoenix VAL-MS 580-ST-2 class surge protector 2920434

Created on:2025-02-19 14:32