Phoenix UK 10-TWIN-PE-ground terminal 3001433, ground terminal, wiring method: screw connection, rated wiring capacity: 10mm2, cross section: 0.5 mm2 -16mm2, installation method: NS 35/7,5, NS 35/15, NS 32, color: yellow and green
| Product Type |
Ground terminal |
| connection quantity |
3 |
| Rows |
2 |
| insulation characteristics |
| Overvoltage Category |
III |
| pollution level |
3 |
| Rated surge voltage |
8 kV |
| rated conditions |
1.82W |
| the number of connections per layer |
3 |
| Rated cross section |
10 mm² |
| 1 Upper 1 2 Lower 1 |
| thread |
M4 |
| Considerations |
Note the ampacity of the DIN rail. |
| Tightening torque |
1.5 ... 1.8 Nm |
| stripping length |
11mm |
| plug gauge |
A6 |
| connection meets standards |
IEC 60947-7-2 |
| Rigid conductor cross section |
0.5 mm² ... 16 mm² |
| cross section AWG |
20 ... 6 (as amended by IEC standards) |
| Flexible Wire Cross Section |
0.5 mm² ... 10 mm² |
| WIRE CROSS SECTION, FLEXIBLE [AWG] |
20 ... 8 (as amended by IEC standards) |
| Flexible conductor cross-section (sleeve without plastic insulation) |
0.5 mm² ... 10 mm² |
| flexible conductor cross-section (sleeve with plastic insulating tube) |
0.5 mm² ... 6 mm² |
| Rated cross section |
10 mm² |
| width |
10.2mm |
| height |
56.5mm |
| NS 32 Depth |
64mm |
| NS 35/7,5 depth |
59mm |
| NS 35/15 Depth |
66.5mm |
| color |
green and yellow |
| flame retardant rating, according to UL 94 |
V0 |
| Insulation Material Group |
I |
| insulation material |
PA |
| Application of Static Insulation Materials at Low Temperature |
-60°C |
| insulating materials (DIN EN 60216-1(VDE 0304-21)) |
130°C |
| Insulation Relative Temperature Index (Electrical, UL 746 B) |
130°C |
| railway vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
| Fire protection of railway vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
| railway vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
| Fire protection of railway vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |
| Thermal Release NFPA 130 (ASTM E 1354) |
28 MJ/kg |
| Surface Flammability NFPA 130 (ASTM E 162) |
through |
| Smoke specific optical density NFPA 130 (ASTM E 662) |
through |
| Smoke Toxicity NFPA 130 (SMP 800C) |
through |
| Overview |
| Terminal Installation |
1.5 Nm ... 1.8 Nm (PE feet with mounting screws, M4) |
| Mechanical parameters |
| Open Side Panel |
No |
| Oscillation/Broadband Noise |
| Specifications |
DIN EN 50155 (VDE 0115-200):2018-05 |
| spectrum |
Class 2, Class B service life test, carried out on bogies |
| frequency |
f1= 5Hz to f2= 250Hz |
| ASD rating |
6.12 (m/s²)²/Hz |
| acceleration |
3.12g |
| Test cycle per axis |
5 h |
| Test Direction |
X-, Y-and Z-axes |
| Results |
has passed the test |