Phoenix PSR-SCP- 24UC/ESAM4/2X1/1X2-safety relay 2900525, safety relay, used for emergency stop and safety door monitoring, safety level up to EN ISO 13849 standard SIL 3 or Cat. 4, PL e, dual channel operation, 2 enable current paths, rated input voltage: 24V DC, plug-in screw terminal

Application Description
Application Description for industrial applications only

Product Type safety relay
Product Series PSRclassic
Application Emergency stop button
safety door
control dual channel
mechanical life about 107Switch Times
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3

rated conditions 16.44W (US= 26.4 V, IL² = 72 A²,PTotal max= 2.04W +14.4 W)
Rated operating mode 100% Eligible
Electrical clearance and creepage distance between power supply circuits
Rated insulation voltage 250V
rated overvoltage/insulation See chapter "Insulation Coordination"

Overview
Rated control circuit supply voltage US 24V DC -15 % / +10%
US Typical 1.68W (DC)
Rated control supply current IS Typical 70 mA
to UNas reference 0.85 ... 1.1
UN 70 mA DC (at Us)
Impulse current < 3.5 A (&Delta;t = 3 ms Us)
< 100 mA (&Delta;t = 500 ms,Us/Ix)
> -100 mA (&Delta;t = 300 ms,Us/Ix)
< 6 mA (Us/Ixto S34)
< 6 mA (Us/Ixto S35)
power consumption Typical 38 mA (S12)
Typical -38 mA (S22)
typical value 0 mA (Us/Ixto S34)
typical value 1 mA (Us/Ixto S35)
input/start and feedback circuit voltage approx. 24V DC
delay time 5 ms (at A1, at the voltage dip Us)
Test pulse not allowed
Typical Response Time 100 ms (monitoring/manual start)
150 ms (auto start)
Typical startup time (Us) 250 ms (when controlled via A1)
Typical release time 20 ms (via sensor loop as required)
45 ms (via A1 as required)
parallel
Recovery Time 1 s (in accordance with the requirements of safety functions)
< 1 s (start-up time)
protection circuit Surge protection; Suppressor diode
Allowable Total Conductor Resistance approx. 50 Ω (US)
Operating voltage display Green LED
Status Display LED (green)

Contact Type 2 normally open safety contact outputs
1 signal transmission current path
Contact Material AgSnO2,+ 0.2 &micro;m Au
maximum switching voltage 250V AC/DC
Minimum Switching Voltage 10V AC/DC
limit continuous current 6 A (note attenuation and load limit curves)
Maximum starting current 6 A
Minimum impulse current 10 mA
the square of the total current value 72 A2(normally open safety contact output)
36 A2(signal current path 31/32)
Maximum power rating (resistive load) See Load Limit Curve
Minimum on-off capacity 100 mW
switching capacity according to IEC 60947-5-1 6 A (DC13, enable current path)
5 A (AC15, enable current path)
2 A (DC13, signal current path)
1.5 A (AC15, signal current path)
output fuse 10 A gL/gG (normally open safety contact output)
4 A gL/gG (Low Demand Enable Current Path)
6 A gL/gG (signal transmission current path)

Phoenix PSR-SCP- 24UC/ESAM4/2X1/1X2-Safety Relay 2900525