Phoenix IB IL AI 2/SF-230-PAC-Analog Module 2861577,Inline, Analog Input Module, Analog Input: 2,0V ... 10V,-10V ... 10V,0 mA ... 20 mA,4 mA ... 20 mA,-20 mA ... 20 mA, Connection Technology: 2-Wire System, Local Bus Transmission Rate: 500 kBit/s, 3 dB Base Frequency at 230Hz, degree of protection: IP20, including Inline connector and identification area
width
12.2mm
height
136.8mm
depth
71.5mm
Notes on dimensional data
Shell Size
Application Description
Application Description
for industrial applications only
Inline Local Bus
interfaces
2
Connection Mode
Inline data span block
transmission speed
500 kBit/s
Module
ID Code (dec.)
127
Hex ID Encoding
7F
Length Encoding (Hexadecimal)
02
length encoding (decimal)
02
Process Data Channel
32 bits
Input Address Area
4 Byte
Output Address Area
4 Byte
Register Length
32 bits
the required parameter data
6 Byte
the required configuration data
4 Byte
simulation: overview
Enter Name
Analog Input
Input Description
Unidirectional voltage or current input
Input Quantity
2
A/D conversion time
Typical 120 & micro;s per channel
Connection Mode
Inline Shielded Connector
connection system
2 wire system
Notes on connection technology
Shielding
current input signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
input current
50Ω (in parallel)
voltage input signal
0V ... 10V
-10V ... 10V
input voltage
> 220 kΩ
data format
IB IL,IB ST,IB RT, Standardized Display
cut-off frequency (3dB)
230Hz
Signal-to-ground common mode voltage range
40V (between current input and functional ground)
40V (between voltage input and functional ground)
measuring principle
successive approximation
Measurement value resolution
16 bits (15 bits + sign bit)
measurement value expression
16-bit two's complement
protection circuit
surge protection; suppressor diode in analog input
Product Type
I/O components
product series
Inline
type
Module
Scope of supply
includes Inline connector and identification area
Mode of operation
2 words of process data manipulation
special nature
3 dB fundamental frequency at 230Hz
diagnostic information
Internal I/O Power Failure Yes
peripheral fault process data
error message in user error procedure data
Phoenix IB IL AI 2/SF-230-PAC-Analog Module 2861577