| Direction of action |
Line-Line & Line-Earth Ground |
| Maximum continuous voltage Uc |
185V DC |
| 130V AC |
| Rated current |
450 mA AC (45 °C) |
| 130 mA DC (45 °C) |
| UC, the effective working current IC |
≤ 10 µA |
| Residual Flow IPE |
≤ 10 µA |
| Nominal discharge current In(8/20) & micro;s (core-core) |
10 kA |
| Rated discharge current In(8/20)& micro;s (core-ground) |
10 kA |
| pulse discharge current Iimp(350) & micro;s (core-core) |
1 kA |
| pulse discharge current Iimp(350) & micro;s (core-ground) |
1 kA |
| Total discharge current Itotal(8/20) µs |
18 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-ground) |
18 kA |
| rated power pulse current lan (700)& micro;s (core-core) |
100 A |
| rated power pulse current lan (700)& micro;s (core-ground) |
100 A |
| Output voltage limit 1 kV/& micro;s (core-to-core) peak |
≤ 300V |
| Output voltage limit 1 kV/& micro;s (core-ground) peak |
≤ 300V |
| Output voltage limit 1 kV/& micro;s (core-core) static |
≤ 300V |
| Output voltage limit 1 kV/& micro;s (core-ground) static |
≤ 300V |
| Residual voltage ln,(wire-wire) |
≤ 160V (C2 - 10 kV / 5 kA) |
| Residual voltage ln,(wire-ground) |
≤ 200V (C2 - 10 kV / 5 kA) |
| voltage protection level Up(core-core) |
≤ 250V (B2 - 1 kV / 25 A) |
| ≤ 300V (B2 - 4 kV / 100 A) |
| ≤ 270V (C1 - 1 kV / 500 A) |
| ≤ 300V (C2 - 2 kV/1 kA) |
| ≤ 320V (C2 - 4 kV / 2 kA) |
| ≤ 330V (C2 - 10 kV / 5 kA) |
| voltage protection level Up(line-ground) |
≤ 250V (B2 - 1 kV / 25 A) |
| ≤ 300V (B2 - 4 kV / 100 A) |
| ≤ 270V (C1 - 1 kV / 500 A) |
| ≤ 300V (C2 - 2 kV/1 kA) |
| ≤ 320V (C2 - 4 kV / 2 kA) |
| ≤ 330V (C2 - 10 kV / 5 kA) |
| response time tA(core-core) |
≤ 500 ns |
| response time tA (core-ground) |
≤ 500 ns |
| input attenuation AE, symmetrical. |
Typical 0.4 dB (≤ 5 MHz / 100 Ω) |
| cut-off frequency fg(3 dB),100 Ω symmetric system |
Typical 20 MHz |
| capacitance (core-core) |
Typical 30 pF (f = 1 MHz/VR= 0 V) |
| capacitance (core-ground) |
Typical 30 pF (f = 1 MHz/VR= 0 V) |
| the resistance of each path |
2.2 Ω ± 10% |
| Surge protection fault alarm |
None |
| Impact tolerance (line-line) |
B2 - 4 kV / 100 A |
| C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA |
| C3 - 25 A |
| D1 - 1 kA |
| Impact resistance (line-ground) |
B2 - 4 kV / 100 A |
| C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA |
| C3 - 25 A |
| D1 - 1 kA |