Phoenix PT 3-PB-ST-Surge Protector-Plug-in 2858030, surge protection plug, installed on the base, used for regular mode voltage coarse/fine protection of 2 floating ground signal lines in IT system, And common mode voltage ground coarse protection.

Product Type Information Technology
Product Series PLUGTRAB PT
IEC Category C1
C2
C3
D1
VDE requirement level C1
C2
C3
D1
type needle type
Bits 2
can test protectors using the CHECKMASTER software tests:
line pairs per module 3
insulation characteristics
Overvoltage Category III
pollution level 2

Rated voltage UN 5V DC

Connection Mode screw connection (connection to the base)
thread M3
Tightening torque 0.8 Nm
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Connectable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 17.7mm
height 45mm
depth 52mm
Horizontal stitch pitch 1 Partition
full module width 17.7mm
Full module height 90mm
full module depth 65.5mm

color black (RAL 9005)
flame retardant rating, according to UL 94 V-0
Shell Material PA

Mechanical parameters
Open Side Panel No

Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage Uc 5.2V DC
3.6V AC
Rated current 450 mA (45°C)
UC, the effective working current IC ≤ 300 µA
Residual Flow IPE ≤ 300 & micro;A (with PT 1X2-BE)
≤ 1 & micro;A (with PT 1X2 F-BE)
Rated discharge current In(8/20)& micro;s (core-ground) 10 kA
pulse discharge current Iimp(10/350) µs 2.5 kA
Total discharge current Itotal(8/20) µs 20 kA
Maximum discharge current Imax(8/20) & micro;s (core-core) 10 kA
Maximum discharge current Imax(8/20) & micro;s (core-ground) 10 kA
rated power pulse current lan (1000)& micro;s (core-core) 90 A
Output voltage limit 1 kV/& micro;s (core-to-core) peak ≤ 55V
Output voltage limit 1 kV/& micro;s (core-ground) peak ≤ 55V (with PT 1X2-BE)
≤ 700V (with PT 1X2 F-BE)
Output voltage limit 1 kV/& micro;s (core-core) static ≤ 15V
Output voltage limit 1 kV/& micro;s (core-ground) static ≤ 15V
≤ 30V (with PT 1X2 F-BE)
residual voltage ln,(wire-wire) ≤ 15V
residual voltage ln,(wire-ground) ≤ 30V (with PT 1X2-BE)
In(line-signal ground) ≤ 15V (with PT 1X2-BE)

Phoenix PT 3-PB-ST-Surge Protector-Plug and Plug 2858030