Phoenix PSR-SCP- 24DC/FSP/1X1/1X2-coupling relay 2981978, safety coupling relay, suitable for SIL 3 high-demand and low-demand applications, can connect digital output signals to peripherals, 1 enable current path, 1 Signal contact, module suitable for safe state shutdown applications, test pulse filter, fuse, plug-in screw connection, width: 17.5mm

Product Type coupling relay
Product Series PSRclassic
Application Safety Shutdown
high requirements
low requirements
control single channel
mechanical life 10x 106Switch Times
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2

rated conditions 2.4W
Rated operating mode 100% Eligible
Rated insulation voltage 250V AC
rated overvoltage/insulation control circuit A1/A2), (21/22), (13/14) between the enhanced safety isolation withstand voltage 6 kV

Overview
Rated control circuit supply voltage US 24V DC -15 % / +10%
US Typical 1.32W
Rated control supply current IS 55 mA typical
Input Voltage Range 20.4V DC ... 26.4V DC
Impulse current Max. 100 mA
filter time max. 5 ms (at A1, at the voltage dip Us)
max. 2 ms (test pulse width; high test pulse at A1/A2)
≥ 100 ms (test pulse width; high test pulse at A1/A2)
test pulse rate = 80 x test pulse width
max. 5 ms (test pulse width; low test pulse at A1/A2)
≥ 50 ms (test pulse rate; low test pulse at A1/A2)
test pulse rate = 15 x test pulse width
Typical startup time (Us) 50 ms
Typical release time 50 ms
Recovery Time 1 s
Maximum switching frequency 0.5Hz
protection circuit Surge protection; Suppressor diode, 33V (A1-A2)
Operating voltage display 1 x yellow LED

Contact Type 1 starting current path
1 feedback loop
Contact Material AgCuNi,+ 0.2 µm Au
maximum switching voltage 250V AC/DC (normally open contact, normally closed contact, pay attention to the load curve)
Minimum Switching Voltage 15V AC/DC (normally open contact/normally closed contact)
limit continuous current 5 A (N/O contact, note attenuation)
100 mA (normally closed contact)
Maximum impact current 5 A (N/O contact)
100 mA (normally closed contact)
Minimum impulse current 5 mA (normally open contact/normally closed contact)
the square of the total current value 25 A2(pay attention to capacity reduction)
Maximum power rating (resistive load) 120W (24V DC,& tau;= 0ms, normally closed contact: 2.4W)
192W (48V DC,& tau;= 0ms, normally closed contact: 4.8W)
162W (60VDC,& tau; = 0ms, normally closed contact: 6W)
66W (110V DC,& tau;= 0ms, normally closed contact: 11W)
60W (220V DC,& tau;= 0ms, normally closed contact: 22W)
1250 VA (250V AC,& tau; = 0 ms, normally closed contact: 25VA)
Maximum power rating (inductive load) 72W (24V DC,& tau;= 40ms, normally closed contact: 2.4W)
43W (48V DC,& tau;= 40ms, normally closed contact: 4.8W)
41W (60VDC,& tau; = 40ms, normally closed contact: 6W)
35W (110V DC,& tau;= 40ms, normally closed contact: 11W)
48W (220V DC,& tau;= 40ms, normally closed contact: 22W)
On-Off Capacity 75 mW minimum
on-off capacity (3600/h cycle) 5 A (24V (DC13))
5 A (230V (AC15))
output fuse 5 A T-fuse (N/O contact)
150 mA fast fuse (normally closed contact)

connection technology
pluggable is
Wire Connection
Connection Mode screw connection
Rigid conductor cross section 0.2 mm² ... 2.5 mm²
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Wire Cross Section AWG 24 ... 12
stripping length 7mm
thread M3

width 17.5mm
height 99mm
depth 114.5mm

Phoenix PSR-SCP- 24DC/FSP/1X1/1X2-Coupling relay 2981978

Created on:2025-06-12 09:27

News Dynamics