Phoenix PSR-SCP- 24DC/URM4/4X1/2X2/B-expansion module 2981677, single-channel contact expansion module with TBUS interface, 4 normally open contacts, 1 normally closed contact, 1 confirmed current path, no delay, meets Cat. 4 and PL e requirements of EN ISO 13849 standard, plug-in screw terminal, width: 22.5mm
Product Type
safety relay
product series
PSRclassic
Application
Expansion Module
control
single channel
mechanical life
about 107 Switch Times
Relay Model
Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level
III
pollution level
2
Typical startup time (Us )
10 ms (when controlled via K1/K2)
Typical release time
10 ms (when requested via K1/K2)
Electrical characteristics
rated conditions
16.14W (UN = 26.4 V, IL ² = 72 A², PTotal max = 1.74W +14.4 W)
Rated operating mode
100% Eligible
Rated insulation voltage
250V
rated overvoltage/insulation
4kV/basic safety isolation (6kV enhanced safety isolation between input loop/normally closed contact and normally open safety contact output).
input data
digital quantity: K1/K2
Input Description
safety related
Input Quantity
1
input voltage range, "1" signal
21.6V DC ... 26.4V DC
Impulse current
< 130 mA (Δt = 800 ms)
protection circuit
suppression diode
power consumption
Typical 60 mA
Output Data
relays: enabling current paths
Output Description
2 normally open contacts each in series, safety-related, floating
outputs
4
Contact Type
4 normally open safety contact outputs
Contact Material
AgSnO2
Switching voltage
Minimum 5V AC/DC
Max. 250V AC/DC
On-Off Capacity
50 mW minimum
Impulse current
10 mA minimum
max. 6 A
limit continuous current
6 A (note attenuation and load limit curves)
the square of the total current value
72 A2 (pay attention to capacity reduction)
Switching frequency
max. 0.5Hz
mechanical life
10x 106 Switch Times
output fuse
10 A gL/gG
4 A gL/gG (for low-demand applications)
Relays: Way Feedback Loops (11/12)
Output Description
diagnostic contacts, 2 series normally closed contacts, floating
outputs
1
Contact Type
2 series normally closed contacts, floating
Contact Material
AgSnO2
Switching voltage
Minimum 5V AC/DC
26.4V AC/DC Max
On-Off Capacity
50 mW minimum
Impulse current
10 mA minimum
max. 6 A
limit continuous current
1 A
the square of the total current value
1 A2
Switching frequency
max. 0.5Hz
mechanical life
10x 106 Switch Times
output fuse
1 A gL/gG
Relays: Signal Transmission Current Path (61/62)
Output Description
2 parallel normally closed contacts, floating
outputs
1
Switching voltage
Minimum 5V AC/DC
250V AC/DC
On-Off Capacity
50 mW minimum
Impulse current
10 mA minimum
max. 6 A
limit continuous current
1 A
the square of the total current value
1 A2
Switching frequency
max. 0.5Hz
mechanical life
10x 106 Switch Times
output fuse
1 A (gL/gG)