Phoenix EMD-FL-C-10-monitoring relay 2866022, monitoring relay for 0...10 A AC 1-phase current monitoring, overcurrent/undercurrent or window function, fault recording, wide-area power supply, 2 PDT
Product Type
Current monitoring relay
Mode of operation
100% operating factor
mechanical life
about 2x 107times
insulation characteristics
insulation
Foundation Isolation
Overvoltage Category
III
pollution level
2
service life, electrical
2x 105times, resistive load 1000 VA
rated conditions
1W
Main Power Type
single phase
Rated insulation voltage
300V
Rated overvoltage
4 kV
power supply
Supply Voltage Range
24V AC ... 240V AC -15 % ... +10%
24V DC ... 240V DC -20 % ... +25%
Rated power consumption
4.5 VA (1.5 W)
Enter Name
Measurement Input
measured value
DC, AC sinusoidal
Input current range
0 mA ... 100 mA (Terminal blocks: I1 and GND)
0 A ... 1 A (terminal blocks: I2 and GND)
0 A ... 10 A (terminal blocks: I3 and GND)
Overload
800mA( IN= 100mA)
3A( IN= 1A)
12A( IN= 10A)
input current
470 mΩ (IN= 100 mA)
47 mΩ (IN= 1 A)
5 mΩ (IN= 10 A)
Frequency Range
48Hz ... 400Hz
maximum temperature coefficient
< 0.1 %/K
Response Delay Setting Range
0.1 s ... 10 s
Start-up delay setting range
0 s ... 10 s
Minimum setting range
5 % ... 95 % (IN)
Maximum setting range
10 % ... 100 % (IN)
Function
Overcurrent
under current
window
memory error
basic accuracy
± 5% (final value)
Setting Accuracy
≤ 5% (final value)
repeat accuracy
≤ 2%
Recovery Time
500 ms
switching
Contact Type
2 floating transfer contacts
maximum switching voltage
250V AC (according to IEC 60664-1)
Maximum power rating (resistive load)
750 VA (3 A/250V AC, module arrangement, spacing ≤ 5mm)
1250 VA (5 A/250V AC, modules not arranged, spacing ≥ 5mm)