Phoenix RIF-2-RPT-LDP-24DC/4X21/EX-relay module 2909741, prefabricated relay module includes: relay base, plug-in functional module, power contact relay and bracket, has been certified according to ATEX/IECEx (zone 2) and explosion-proof area level I and zone 2 Requirements, in-line connection, 4 PDT, freewheeling diode, input voltage: 24V DC
Product Type
Relay Module
Product Series
RIFLINE complete
Application
Class I, Part 2
Potential Explosion Area
Mode of operation
100% operating factor
mechanical life
about 2x 107times
insulation characteristics
insulation
Foundation Isolation
Overvoltage Category
III
II (Zone 2)
Data Management Status
Last data maintenance date
20.03.2025
rated conditions
1.01W
test voltage (coil/contact)
2.5 kVrms(50Hz,1 min, coil/contact)
test voltage (contact/contact)
2 kVrms(50Hz,1 min, contact/contact)
Rated insulation voltage
250V AC
Rated overvoltage
2.5 kV
coil side
Rated input voltage UN
24V DC
Input Voltage Range
19.2V DC ... 30V DC (20 °C)
to UNas reference
See Graph
drives and functions
monostable
drive (polarity)
polarization
UN
42 mA
Typical Response Time
13 ms
Typical release time
14 ms
coil voltage
24V DC
protection circuit
freewheeling diode
Operating voltage display
yellow LED
switching
Contact Type
4 PDT
Switch Contact Type
single contact
Contact Material
AgNi
maximum switching voltage
250V AC/DC
Minimum Switching Voltage
5V (24 mA)
limit continuous current
6 A (see graph)
Maximum impact current
16 A (20 ms, normally open contact)
minimum switching current
5 mA (24 V)
Maximum power rating (resistive load)
144W (24V DC)
124W (available for 48V DC)
108W (available for 60V DC)
52W (available for 110V DC)
48W (available for 220V DC)
1500 VA (available for 250V AC)
switch capacity
2 A (24V, DC13)
0.22 A (120V, DC13)
0.11 A (250V, DC13)
1.5 A (24V, AC15)
1.5 A (120V, AC15)
1 A (240V, AC15)
Connection Mode
in-line connection
stripping length
8mm
Rigid conductor cross section
0.14 mm² ... 1.5 mm²
Flexible Wire Cross Section
0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm² (cold press head with plastic sleeve)
0.14 mm² ... 1 mm² (sleeve with plastic insulating sleeve, two wires on the two-position terminal)