| Overview |
| working voltage |
18V DC ... 30V DC |
| Rated voltage |
24V DC |
| Nominal operating current IN |
max. 32 A DC (IN +) |
| max. 40 A DC (each terminal point position when additional equipment is bridged via IN +) |
| Nominal operating current IN |
1 / 2 / 3 / 4 / 5 / 6/7/8 A DC (each output channel is adjustable) |
| Rated current (pre-adjusted) |
4 A |
| Rated overvoltage |
0.5 kV |
| Breaking method |
EG (Electronic-Physical Separation) |
| feedback resistance |
Max 35V DC |
|
only in I of the power supplymax> Short circuit switching capacity when required. Built-in fail-safe element. |
| 30 A (gG, linear power supply, Icn≥ 200 A) |
| Short-circuit switch capacity |
300 A |
| dielectric strength |
Max 35V DC (load circuit) |
| Fuse |
electronic |
| efficiency |
> 99% |
| closed-circuit current I0 |
Typical 75 mA |
| power consumption |
Typical 1.8W (no load operation) |
| < 7W (normal operation) |
| Module Initialization Time |
1.6 s |
| wait time after closing a channel |
5 s (overload/short circuit) |
| Measurement Tolerance I |
± 15% |
| temperature attenuation |
25 A DC (at 60°C) |
| 28 A DC (temperature 56°C) |
| 32 A DC (temperature 52°C) |
| MTBF (IEC 61709, SN 29500) |
5000000 h (25°C, 21% load) |
| 2000000 h (40°C at 34.25% load) |
| 321056 h (at 52°C, 100% load) |
| fail-safe components |
15 A DC (per output channel) |
| Contact Type |
relay, normally open contact |
| Load Circuit |
| Downtime |
≤ 10 ms (for short circuit> 2.0 x IN) |
| 1 s (1.2 ... 2.0 x IN) |
| undervoltage shutdown |
≤ 17.8V DC (active) |
| ≥ 18.8V DC (passive) |
| Overvoltage shutdown |
≥ 30.5V DC (active) |
| ≤ 29.5V DC (passive) |
| Maximum capacitive load |
45000 & micro;F (depending on current setting and available short-circuit current) |
| impact suppression |
0.1 s (per output channel) |
| indicator/remote signaling |
| Connection Name |
remote signaling alarm circuit |
| switching function |
N/O contacts |
| Nominal operating voltage |
0V DC ... 30V DC |
| Operating current |
100 mA DC |