Phoenix CAPAROC E2 12-24DC/1-4A EX-Electronic equipment circuit breaker 1344361,2-channel electronic circuit breaker module, can protect 12V DC and 24V DC loads from overload and short circuit. The rated current can be adjusted between 1 A and 4 A by means of a step switch. Explosion proof zone 2 certified. The product is DIN-rail mounted via CAPAROC bus bars.

Product Type Equipment circuit breaker
Product Series CAPAROC
type plug-in module
Bits 1
Channels 2
slots 2
insulation characteristics
protection level III
pollution level 2

Overview
working voltage 10V DC ... 30V DC
Rated voltage 12V DC
24V DC
Nominal operating current IN 4 A DC (per channel)
Nominal operating current IN 1 / 2/3/4 A DC (adjusted by rotary code switch)
1 / 2/3/4 A DC (in RC mode, it can be set through the power module with communication interface)
Rated current (preset) 1 A
Rated overvoltage 0.5 kV
Breaking method E (Electronic)
feedback resistance Max 35V DC
impact suppression 50 ms (each channel is preset by default)
works with CAPAROC PM IOLs and CAPAROC PM PN power modules
only in I of the power supplymax> Short circuit switching capacity when required. Built-in fail-safe element.
Short-circuit switch capacity 300 A
dielectric strength 35V DC (load circuit)
Active Current Limit Typical value at IN≤ 3 AN
IN= 4 A, it is usually 1.5 x IN
Fuse electronic
efficiency > 99%
closed-circuit current I0 Typical 25 mA (no load at 24V)
power consumption Typical 0.6W (no load at 24V)
< 1.1W (normal operation at 24V,4 A)
Measurement Tolerance I ± 10 % (2 A ... 4 A)
± 20 % (1 A)
MTBF (IEC 61709, SN 29500) 11364927 h (25°C, 21% load)
5271554 h (40°C at 34.25% load)
640731 h (100% load at 65°C)
voltage drop 0.06V (at 4 A)
fail-safe components 5 A DC (per output channel)
Contact Type without electrical isolation
Load Circuit
Downtime 5 s (IN≥ 4 A… 1.3 x IN)
5 s (in IN< 4 A… 1.7 x IN)
≤ 400 ms (maximum 450 ms for large starting current)
Typical 20 ms (for short circuit> 1.5 x IN)
undervoltage shutdown ≤ 8.5V DC (active)
≥ 9.2V DC (passive)
Overvoltage shutdown ≥ 32.5V DC (active)
≤ 30.5V DC (passive)
Maximum capacitive load ≤ 60000 & micro;F (depending on current setting and available short-circuit current)

fuse protection output
Connection Mode in-line connection
stripping length 10mm
Flexible Wire Cross Section 0.2 mm² ... 4 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12
Flexible conductor cross-section, with sleeve, with plastic insulation sleeve 0.25 mm² ... 4 mm²
flexible conductor cross-section with cold press head without insulation sleeve 0.25 mm² ... 4 mm²

Phoenix CAPAROC E2 12-24DC/1-4A EX-Electronic Equipment Circuit Breaker 1344361