| Overview |
| working voltage |
10V DC ... 30V DC |
| Rated voltage |
12V DC |
| 24V DC |
| Nominal operating current IN |
10 A DC (per channel) |
| Nominal operating current IN |
2 / 4 / 6/8/10 A DC (adjusted by rotary code switch) |
| 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8/9/10 A DC (in RC mode, it can be set through the power module with communication interface) |
| Rated current (pre-adjusted) |
2 A |
| Rated overvoltage |
0.5 kV |
| Breaking method |
E (Electronic) |
| feedback resistance |
Max 35V DC |
| impact suppression |
50 ms (each channel is preset by default) |
| works with CAPAROC PM IOLs and CAPAROC PM PN power modules |
|
only in I of the power supplymax> Short circuit switching capacity when required. Built-in fail-safe element. |
| Short-circuit switch capacity |
300 A |
| dielectric strength |
35V DC (load circuit) |
| Active Current Limit |
Typical value at IN≤ 3 AN |
| Typical value at IN≥ 4 AN |
| Fuse |
electronic |
| efficiency |
> 99% |
| closed-circuit current I0 |
Typical 25 mA (no load at 24V) |
| power consumption |
Typical 0.6W (no load at 24V) |
| < 3.3W (in normal operation at 24V and 10 A) |
| Measurement Tolerance I |
± 10% (typical) |
| temperature attenuation |
20 A (total current at 40°C) |
| 10 A (total current at 65°C) |
| MTBF (IEC 61709, SN 29500) |
11140621 h (25°C, 21% load) |
| 4699883 h (40°C at 34.25% load) |
| 534110 h (at 40°C, 100% load) |
| voltage drop |
0.14V (at 10 A) |
| fail-safe components |
15 A DC (per output channel) |
| Contact Type |
without electrical isolation |
| Load Circuit |
| Downtime |
5 s (in IN≥ 4 A… 1.3 x IN) |
| 5 s (in IN< 4 A… 1.7 x IN) |
| Typical 400 ms (up to 450 ms for large starting currents) |
| Typical 20 ms (for short circuit> 1.5 x IN) |
| undervoltage shutdown |
≤ 8.5V DC (active) |
| ≥ 9.2V DC (passive) |
| Overvoltage shutdown |
≥ 32.5V DC (active) |
| ≤ 30.5V DC (passive) |
| Maximum capacitive load |
≤ 75000 & micro;F (depending on current setting and available short-circuit current) |