Phoenix CAPAROC E2 12-24DC/2-10A EX-electronic equipment circuit breaker 1344364,2-channel electronic circuit breaker module, can protect 12V DC and 24V DC loads from overload and short circuit. The rated current can be adjusted between 2 A and 10 A by means of a step switch. Explosion proof zone 2 certified. The product is DIN-rail mounted via CAPAROC bus bars.

Product Type Equipment circuit breaker
product series CAPAROC
type Plug-in Modules
Bits 1
Channels 2
slots 2
insulation characteristics
protection level III
pollution level 2

Overview
working voltage 10V DC ... 30V DC
Rated voltage 12V DC
24V DC
Nominal operating current IN 10 A DC (per channel)
Nominal operating current IN 2 / 4 / 6/8/10 A DC (adjusted by rotary code switch)
1 / 2 / 3 / 4 / 5 / 6 / 7 / 8/9/10 A DC (in RC mode, it can be set through the power module with communication interface)
Rated current (preset) 2 A
Rated overvoltage 0.5 kV
Breaking method E (Electronic)
feedback resistance Max 35V DC
impact suppression 50 ms (each channel is preset by default)
works with CAPAROC PM IOLs and CAPAROC PM PN power modules
required spare fuse only in I of the power supplymax> Short circuit switching capacity when required. Built-in fail-safe element.
Short-circuit switch capacity 300 A
dielectric strength 35V DC (load circuit)
Active Current Limit Typical value at IN≤ 3 AN
Typical value at IN≥ 4 AN
Fuse electronic
efficiency > 99%
closed-circuit current I0 Typical 25 mA (no load at 24V)
power consumption Typical 0.6W (no load at 24V)
< 3.3W (in normal operation at 24V and 10 A)
Measurement Tolerance I ± 10% (typical)
temperature attenuation 20 A (total current at 40°C)
10 A (total current at 65°C)
MTBF (IEC 61709, SN 29500) 11140621 h (25°C, 21% load)
4699883 h (40°C at 34.25% load)
534110 h (at 40°C, 100% load)
voltage drop 0.14V (at 10 A)
fail-safe components 15 A DC (per output channel)
Contact Type without electrical isolation
Load Circuit
Downtime 5 s (in IN≥ 4 A… 1.3 x IN)
5 s (in IN< 4 A… 1.7 x IN)
Typical 400 ms (up to 450 ms for large starting currents)
Typical 20 ms (for short circuit> 1.5 x IN)
undervoltage shutdown ≤ 8.5V DC (active)
≥ 9.2V DC (passive)
Overvoltage shutdown ≥ 32.5V DC (active)
≤ 30.5V DC (passive)
Maximum capacitive load ≤ 75000 & micro;F (depending on current setting and available short-circuit current)

fuse protection output
Connection Mode in-line connection
stripping length 10mm
Flexible Wire Cross Section 0.2 mm² ... 4 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Connectable Guide Cross Section AWG 24 ... 12
Flexible conductor cross-section, with sleeve, with plastic insulation sleeve 0.25 mm² ... 4 mm²
flexible conductor cross-section with cold press head without insulation sleeve 0.25 mm² ... 4 mm²

Phoenix CAPAROC E2 12-24DC/2-10A EX-Electronic Equipment Circuit Breaker 1344364