Phoenix STEP3-PS/1AC/12DC/5/PT-power supply 1170955, primary switching power supply, STEP POWER, in-line connection, DIN rail or direct installation, input: 1 phase, output: 12V DC/5 A, adjustable range 9V DC ... 17V DC
AC operation
Power System Configuration
star network (TN,TT,IT (PE))
Input Voltage Range
100V AC ... 240V AC -15 % ... +10%
115V AC ... 240V AC ±10 % (UL)
Attenuation
< 100V AC ... 85V AC (1 %/V)
National Grid Typical Voltage
120V AC
230V AC
Supply Voltage
AC/DC
Impulse current
Typical 35 A (25°C)
impulse current integral (I2t)
Typical 0.6 A2s
frequency range (fN)
50Hz ... 60Hz ± 10%
grid buffer time
Typical 30 ms (120V AC)
Typical 130 ms (230V AC)
power consumption
1.2 A (100V AC)
0.64 A (240V AC)
protection circuit
transient surge protection; varistor
Suction time
Typical 2 s
Device Power Fuse
4 A built-in (device protection) slow fuse
recommend use
6 A ... 16 A (characteristics B, C, D, K)
PE discharge current
< 0.25 mA
DC operation
Input Voltage Range
110V DC ... 250V DC -20 % ... +10%
120V DC ... 150V DC ±10 % (UL)
Attenuation
< 110V DC ... 88V DC (1 %/V)
power consumption
0.61 A (110V DC)
0.26 A (250V DC)
efficiency
> 89 % (120V AC)
> 90 % (230V AC)
Efficiency Level
VI
Rated output voltage
12V DC
output voltage (USet) setting range
9V DC ... 16.5V DC (> 12V DC, limited stable capacity)
Rated output current (IN)
5 A
Short-circuit protection
is
Anti-aircraft turn
is
Attenuation
> 50°C ... 70°C (2 % / K)
amplitude factor
Typical 3.69
Typical 4.17
output power (PN)
60W
and connect
, the use of diodes allows for increased power and increased redundancy
Concatenation
Yes, for higher output voltages
feedback voltage resistance
≤ 25V DC
output
< 25V DC
residual wave
Typical 100 mVSS
control deviation
< 0.5 % (static load change 10% ... 90%)
<4% (dynamic load change 10% ... 90%,(10Hz))
< 0.1 % (input voltage variation is ± 10 %)
rise time
typical 100 ms (UOut= 10%... 90%)
minimum no-load power consumption
< 0.21W (120V AC)
maximum no-load power consumption
< 0.21W (230V AC)
minimum rated load power consumption
< 7.5W (120V AC)
Maximum rated load power loss
< 6.9W (230V AC)
Input
Location
1.x
connection technology
Position Identification
1.1, 1.2 (L), 1.3, 1.4 (N)
Wire Connection
Connection Mode
in-line connection
Rigidity
0.2 mm² ... 2.5 mm²
1 mm² (recommend)
flexibility
0.2 mm² ... 2.5 mm²
1 mm² (recommend)
flexible strip cold press head without plastic sleeve
0.5 mm² ... 1.5 mm²
1 mm² (recommend)
flexible strip cold press head with plastic sleeve