Phoenix PT-IQ-1X2 F-24DC-UT-surge protector 2800977, surge protection, including protective plug and base element, built-in multi-segment status indicator on the module, used for a 2-wire floating ground intrinsic safety signal circuit. Indirect grounding through the gas discharge tube. Can be used in safety-related circuits up to SIL 3.
Product Type
measurement and control technology
product series
PLUGTRAB IQ
IEC Category
C1
C2
C3
D1
type
DIN rail module, split, detachable
Surge protection fault alarm
Vision, Multi-Stage
line pairs per module
1
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated voltage UN
24V DC
Connection Mode
screw connection
thread
M3
Tightening torque
0.5 Nm
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Rigid conductor cross section
0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG
24 ... 12
Dimensional drawing
width
17.7mm
height
91.1mm
depth
77.5mm (7.5mm with DIN rail)
Horizontal stitch pitch
1 Partition
color
black (RAL 9005)
black (RAL 9005)
flame retardant rating, according to UL 94
V-0
Shell Material
PA 6.6
Mechanical parameters
Open Side Panel
No
movement direction
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous operating voltage UC
30V DC
21V AC
Rated current
1000 mA (40°C)
UC, the effective working current IC
≤ 1 mA (in signal loop)
Residual Flow IPE
≤ 1 µA
Nominal discharge current In(8/20) & micro;s (core-core)
10 kA
Rated discharge current In(8/20)& micro;s (core-ground)
10 kA
pulse discharge current Iimp(350) & micro;s (core-ground)