| movement direction |
Line-Shield/Earth Ground |
| Maximum continuous operating voltage UC |
70V DC |
| 50V AC |
| Maximum continuous operating voltage UC(core-ground) |
70V DC |
| 50V AC |
| Rated current |
10 A |
| UC, the effective working current IC |
≤ 1 µA |
| Nominal discharge current In(8/20) µs |
5 kA |
| Rated discharge current In(8/20)& micro;s (core-ground) |
5 kA |
| Nominal discharge current In(8/20)& micro;s (core/shield) |
5 kA |
| pulse discharge current Iimp(10/350) µs |
1 kA |
| pulse discharge current Iimp(350) & micro;s (core-ground) |
1 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-ground) |
10 kA |
| Maximum discharge current Imax(8/20) & micro;s (core-shield) |
10 kA |
| rated power pulse current lan (1000)& micro;s (core-shield) |
100 A |
| impulse current (10/350) & micro;s (L-N), peak current Iimp |
1 kA |
| Output voltage limit 1 kV/& micro;s (core-ground) peak |
≤ 650V |
| Output voltage limit 1 kV/& micro;s (core-shield) peak |
≤ 650V |
| Output voltage limit 1 kV/& micro;s (core-ground) static |
≤ 650V |
| output voltage limit 1 kV/& micro;s (core-shield) static |
≤ 650V |
| voltage protection level Up(line-ground) |
≤ 800V (C2 - 4 kV / 2 kA) |
| ≤ 1 kV (C2 - 10 kV / 5 kA) |
| voltage protection level Up(core-shield) |
≤ 800V (C2 - 4 kV / 2 kA) |
| ≤ 1 kV (C2 - 10 kV / 5 kA) |
| response time tA (core-ground) |
≤ 100 ns |
| response time tA (core-shield) |
≤ 100 ns |
| input attenuation AE, asymmetric. |
0.1 dB (≤ 6 GHz) |
| cutoff frequency fg(3 dB), asymmetric. (shielded) in a 50 Ω system |
> 6 GHz |
| Frequency Range |
0Hz ... 6 GHz |
| 50 Ω system |
Typical 1.15 (≤ 6 GHz) |
| Allowable high-frequency power Pmax,VSWR = xx(50 ohm system) |
30W (VSWR=1.15) |
| capacitance (core-ground) |
Typical 1.5 pF |
| Capacitance Asymmetry (Shielded) |
Typical 1.5 pF |
| Surge protection fault alarm |
None |
| Impact resistance (line-ground) |
C2 - 10 kV / 5 kA |
| C3 - 100 A |
| D1 - 1 kA |
| Impact resistance (line-shield) |
C2 - 10 kV/5 kA |
| C3 - 100 A |
| D1 - 1 kA |
| alternating current carrying capacity (wire-shield) |
5 A - 1 s |