Phoenix VAL-MS 230/2 Class 0 - 2 surge protector 2800103, two-position rail-mounted surge protector, 20 protection mode, with temperature monitoring/thermal trip device and visual status indication window.
Rated voltage: 275V AC.

Product Type surge protector
product series VALVETRAB MS
IEC Category II
T2
EN Type T2
IEC power supply system TN-C
type DIN rail module, split, detachable
Surge protection fault alarm with visual status indication window
insulation characteristics
Overvoltage Category III
pollution level 2

Rated frequency fN 50Hz (60 Hz)

Connection Mode screw connection
thread M5
Tightening torque 3 Nm (1.5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
stripping length 16mm
Flexible Wire Cross Section 1.5 mm² ... 25 mm²
Rigid conductor cross section 1.5 mm² ... 35 mm²
Attachable Guide Cross Section AWG 15 ... 2
Connection Mode fork cable end
Flexible Wire Cross Section 1.5 mm² ... 16 mm²

Dimensional drawing
width 35.6mm
height 89.8mm
depth 65.7mm (7.5mm with DIN rail)
Horizontal stitch pitch Division 2

color black (RAL 9005)
flame retardant rating to UL 94 V-0
material 600
insulation material PA 6.6/PBT
Material Group I
Shell Material PA 6.6
PBT

protection channel L-PEN
movement direction 2L-PEN
Rated voltage UN 240/415V AC (TN-C)
Rated frequency fN 50Hz (60 Hz)
Maximum continuous operating voltage UC 275V AC
Rated load current IL 80 A
Residual Flow IPE ≤ 0.9 mA
Standby power consumption PC ≤ 240 mVA
Nominal discharge current In(8/20)µs 20 kA
Maximum discharge current Imax(8/20) µs 40 kA
Rated short-circuit current ISCCR 25 kA
voltage protection level Up ≤ 1.35 kV
Residual pressure Ures ≤ 1.35 kV (In)
≤ 1.1 kV (10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
UT 335V AC (5 seconds/withstand mode)
response time tA ≤ 25 ns
Maximum spare fuse with V-connection wire 80 A (gG)
maximum spare fuse with branch wiring 125 A (gG)

Phoenix VAL-MS 230/2 class 0 - 2 surge protector 2800103