Phoenix VAL-MS 230/2 0-FM-2 surge protector 2800102, two-position rail-mounted surge protector, 20 protection mode, temperature monitoring/thermal tripping device, visual status indication window and remote signaling contact.

Product Type surge protector
Product Series VALVETRAB MS
IEC Category II
T2
EN Type T2
IEC power supply system TN-C
type DIN rail module, split, detachable
Surge protection fault alarm visual status indication window and remote alarm contact
insulation characteristics
Overvoltage Category III
pollution level 2

Rated frequency fN 50Hz (60 Hz)
indicator/remote signaling
Connection Name Remote alarm contact
switching function changeover contact
Nominal operating voltage 5V AC ... 250V AC
30V DC
Operating current 5 mA AC ... 1.5 A AC
1 A DC

Connection Mode screw connection
thread M5
Tightening torque 3 Nm (1.5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
stripping length 16mm
Flexible Wire Cross Section 1.5 mm² ... 25 mm²
Rigid conductor cross section 1.5 mm² ... 35 mm²
Attachable Guide Cross Section AWG 15 ... 2
Connection Mode fork cable end
Flexible Wire Cross Section 1.5 mm² ... 16 mm²
Remote alarm contact
Connection Mode COMBICON in-line/screw connection
thread M2
Tightening torque 0.25 Nm
stripping length 7mm
Flexible Wire Cross Section 0.14 mm² ... 1.5 mm²
Rigid conductor cross section 0.14 mm² ... 1.5 mm²
Attachable Guide Cross Section AWG 28 ... 16

Dimensional drawing
width 35.6mm
height 96.8mm
depth 65.7mm (7.5mm with DIN rail)
Horizontal stitch pitch Division 2

color black (RAL 9005)
flame retardant rating to UL 94 V-0
material 600
insulation material PA 6.6/PBT
Material Group I
Shell Material PA 6.6
PBT

protection channel L-PEN
movement direction 2L-PEN
Rated voltage UN 240/415V AC (TN-C)
Rated frequency fN 50Hz (60 Hz)
Maximum continuous operating voltage UC 275V AC
Rated load current IL 80 A
Residual Flow IPE ≤ 0.9 mA
Standby power consumption PC ≤ 240 mVA
Nominal discharge current In(8/20)µs 20 kA
Maximum discharge current Imax(8/20) µs 40 kA
Rated short-circuit current ISCCR 25 kA
voltage protection level Up ≤ 1.35 kV
Residual pressure Ures ≤ 1.35 kV (In)
≤ 1.1 kV (10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
UT 335V AC (5 seconds/withstand mode)