Phoenix STEP-PS/ 1AC/24DC/0.75/FL-power 2868622, STEP POWER power supply for DIN rail installation, primary switching mode, input: 1 phase, output: 24V DC/0.75 A

AC operation
Rated input voltage range 100V AC ... 240V AC
Input Voltage Range 85V AC ... 264V AC
Supply Voltage AC
Impulse current < 15 A (typical)
impulse current integral (I2t) < 0.1 A2s
AC frequency range 45Hz ... 65Hz
DC Frequency Range 0Hz
grid buffer time Typical 15 ms (120V AC)
Typical 70 ms (230V AC)
power consumption 0.3 A (120V AC)
0.25 A (230V AC)
Rated power consumption 36.9 VA
protection circuit transient surge protection; varistor
power factor (cos phi) 0.58
Typical Response Time < 0.5 s
input fuse 1.25 A (slow fuse, internal)
recommend use 6 A ... 16 A (characteristics B, C, D, K)
DC operation
Input Voltage Range 95V DC ... 250V DC
Supply Voltage DC

efficiency > 84% (230V AC and rated)
output characteristics U/ I
Rated output voltage 24V DC
Output current Imax 1.4 A
Rated output current (IN) 0.75 A (-25°C ... 55 °C)
0.83 A (-25°C ... 40°C constant)
Attenuation 55°C ... 70°C (2.5 %/K)
feedback voltage resistance ≤ 35V DC
output < 35V DC
control deviation <1% (load change, static 10%... 90%)
<2% (change of load, dynamic 10%... 90%)
< 0.1 % (input voltage variation is ± 10 %)
residual wave < 75 mVSS(20 MHz)
output power 18W
peak switching voltage rated load < 15 mVSS(20 MHz)
maximum no-load power consumption < 0.5W
Maximum rated load power loss < 3.6W
rise time < 0.5 s (UOUT(10%... 90%))
and connect Yes, for redundancy and increased capacity
Concatenation is

Input
Connection Mode screw connection
Minimum cross section of rigid conductor 0.2 mm²
Maximum cross section of rigid conductor 2.5 mm²
flexible lead 0.2 mm²
flexible conductor 2.5 mm²
Minimum Wire Cross Section AWG 24
Maximum conductor cross section AWG 12
stripping length 6.5mm
thread M3
Minimum tightening torque 0.5 Nm
Maximum tightening torque 0.6 Nm

Phoenix STEP-PS/ 1AC/24DC/0.75/FL-Power 2868622

Created on:2025-08-09 10:56

News Dynamics