Phoenix PT 2X1VA/S1-230AC-ST-surge protector-plug-in 2880024, PT protection plug with protection circuit, used for high voltage signal protection, dual channel. Rated voltage: 230V AC
| Product Type | measurement and control technology |
| Product Series | PLUGTRAB PT |
| IEC Category | C1 |
| C2 | |
| C3 | |
| D1 | |
| type | needle type |
| can test protectors using the CHECKMASTER software tests: | |
| insulation characteristics | |
| Overvoltage Category | III (UC≤ 300V DC / 300V AC) |
| II (UC= 320V DC / 320V AC) | |
| pollution level | 2 |
| Rated voltage UN | 230V AC (50/60 Hz) |
| Connection Mode | screw connection (connection to the base) |
| thread | M3 |
| Tightening torque | 0.8 Nm |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 17.5mm |
| height | 44.8mm |
| depth | 51.7mm |
| Horizontal stitch pitch | 1 Partition |
| full module width | 17.7mm |
| Full module height | 90mm |
| full module depth | 65.5mm |
| color | black (RAL 9005) |
| flame retardant rating to UL 94 | V-0 |
| Shell Material | PA 6.6 |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | Line-Line & Line-Earth Ground |
| Maximum continuous operating voltage UC | 320V DC |
| 320V AC (50/60 Hz) | |
| Rated current | 26 A AC (30 °C) |
| 1 A DC | |
| UC, the effective working current IC | ≤ 200 µA AC |
| ≤ 10 µA DC | |
| Residual Flow IPE | ≤ 400 µA AC |
| ≤ 20 µA DC | |
| Rated discharge current In(8/20)& micro;s (core-ground) | 2.5 kA |
| pulse discharge current Iimp(10/350) µs | 500 A (per path) |
| Total discharge current ITotal(8/20) µs | 5 kA |
| Output voltage limit 1 kV/& micro;s (core-ground) peak | ≤ 850V |
| Output voltage limit 1 kV/& micro;s (core-ground) static | ≤ 850V |
| voltage protection level Up(line-ground) | ≤ 850V (C1 - 1.4 kV / 0.7 kA) |
| ≤ 1050V (C2 - 5 kV/2,5 kA) | |
| ≤ 820V (C3 - 100 A) | |
| response time tA (core-ground) | ≤ 25 ns |
| input attenuation AE, asymmetric. | Typical 0.3 dB (≤ 500 kHz / 150 Ω) |
| cutoff frequency fg(3 dB), asymmetric. 150 Ω in the system (signal ground) | Typical 1.7 MHz |
| capacitance (core-ground) | Typical 2 nF |
| Surge protection fault alarm | with visual status indication window |
| 25 A AC (gL/gG) | |
| 1 A DC (T) | |
| Impact resistance (line-ground) | C1 - 1.4 kV / 0.7 kA |
| C2 - 5 kV / 2.5 kA | |
| C3 - 100 A | |
| D1 - 500 A |
Phoenix PT 2X1VA/S1-230AC-ST-Surge Protector-Plug 2880024
Created on:2025-08-09 13:38