Phoenix SFP 1-20/230AC-EMC filter surge protection equipment 2859987, equipment protection, in line with Class 3/Class III, with network interference suppression filter to prevent high-frequency interference voltage, used for single-phase power supply network, zero Ground separation (3-wire system: L1, N, PE), with remote signaling contacts.
Product Type
interference suppression filter
Product Series
SFP
type
rail mounting module, monolithic
Bits
2
D, A, I, NL, S, E, FIN, P
Surge protection fault alarm
visual status indication window and remote alarm contact
insulation characteristics
Overvoltage Category
III
pollution level
2
IEC Category
III
T3
EN Type
T3
Ports
Two
Electrical characteristics
indicator/remote signaling
Connection Name
Remote alarm contact
switching function
changeover contact
Nominal operating voltage
12V AC ... 250V AC
250V DC (250 mA DC)
working current
100 mA AC ... 1 A AC
1 A DC (48V DC)
connection data
Connection Mode
screw connection terminal
thread
M3
Tightening torque
0.5 Nm ... 0.6 Nm
4.5 lbf -in. ... 5.5 lbf -in.
Flexible Wire Cross Section
2.5 mm² ... 4 mm²
Rigid conductor cross section
2.5 mm² ... 6 mm²
Attachable Guide Cross Section AWG
14 ... 10
Dimensions
Dimensional drawing
width
112mm
height
86.6mm
depth
79mm
Material Specifications
color
black (RAL 9005)
silver
flame retardant rating, according to UL 94
V-0
insulation material
ABS
Shell Material
Aluminum
mechanical characteristics
Mechanical parameters
Open Side Panel
No
protection circuit
protection channel
L-N
L-PE
N-PE
movement direction
L-N & L(N)-PE
Rated voltage UN
240V AC (TN)
240V AC (TT-only with RCD)
240V AC (IT-only with RCD)
Rated frequency fN
50Hz (60 Hz)
Maximum continuous operating voltage UC
264V AC
Rated load current IL
20 A (40 °C)
Residual Flow IPE
≤ 0.6 mA
Standby power consumption PC
≤ 25 VA (UREF )
≤ 27.5 VA (UC )
Reference test voltage UREF
264V AC
Nominal discharge current In (8/20)µs
5 kA
Combined surge UOC
10 kV (5 kA)
voltage protection level Up
≤ 1 kV
UT (L-N)
350V AC (5 seconds/withstand mode)
457V AC (120 min/safe failure mode)
UT (L-PE)
457V AC (5 seconds/withstand mode)
350V AC (120 min/tolerance mode)
1464V AC (200 ms/safety failure mode)
UT (N-PE)
1200V AC (200 ms/SAFE mode)
response time tA
≤ 25 ns
capacity (L-N)
1 µF ±10%
10 nF ±10 % (X2-275 V)
capacity (L-PE)
2.2 nF ±20 % (Y2-250 V)
capacity (N-PE)
2.2 nF ±20 % (Y2-250 V)
20 A (MCB B/Universal)
16 A (IT-MCB B/General)
input attenuation AE, symmetric.
20 dB (≥ 100 kHz / 50 Ω)
input attenuation AE, asymmetric.
30 dB (≥ 1 MHz / 50 Ω)