Phoenix VAL-SEC-T2-3S-350/40-FM-2 class surge protector 2909635, plug-in surge protector, in line with class 2/class II, used for 3-phase power network, zero ground separation (5-wire system: L1, L2, L3, N, PE), with remote indication contacts. According to VDE 0100-534:2016-10, the 40 kA discharge capacity is related to the SPD at the system supply point.
Product Type
surge protector
Product Series
SEC Family
IEC Category
II
T2
EN Type
T2
IEC power supply system
TN-S
TT
type
DIN rail module, split, detachable
Bits
4
Surge protection fault alarm
visual status indication window and remote alarm contact
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated frequency fN
50Hz (60 Hz)
indicator/remote signaling
Connection Name
Remote alarm contact
switching function
changeover contact
Nominal operating voltage
5V AC ... 250V AC
125V DC (200 mA DC)
Operating current
5 mA AC ... 1 A AC
1 A DC (30V DC)
Connection Mode
screw connection
thread
M5
Tightening torque
4.5 Nm
stripping length
16mm
Flexible Wire Cross Section
2.5 mm² ... 16 mm²
Rigid conductor cross section
2.5 mm² ... 25 mm²
Attachable Guide Cross Section AWG
12 ... 4
Connection Mode
fork cable end
Flexible Wire Cross Section
1.5 mm² ... 6 mm²
Remote alarm contact
Connection Mode
COMBICON in-line/screw connection
thread
M2
Tightening torque
0.25 Nm
stripping length
7mm
Flexible Wire Cross Section
0.14 mm² ... 1.5 mm²
Rigid conductor cross section
0.14 mm² ... 1.5 mm²
Attachable Guide Cross Section AWG
28 ... 16
Dimensional drawing
width
49.2mm
height
97.9mm
depth
74.5mm (7.5mm with DIN rail)
Horizontal stitch pitch
2.7 Partition
color (pin connector)
light gray (RAL 7035)
color (basic element)
gray (RAL 7042)
flame retardant rating, according to UL 94
V-0
material
600
insulation material
PA6.6-FR 20% GF
PBT-FR
Material Group
I
Shell Material
PA 6.6-FR 20 % GF
PBT-FR
protection channel
L-N
L-PE
N-PE
movement direction
3L-N & N-PE
Rated voltage UN
240/415V AC (TN-S)
240/415V AC (TT)
Rated frequency fN
50Hz (60 Hz)
Maximum continuous operating voltage UC(L-N)
350V AC
Maximum continuous operating voltage UC(L-PE)
350V AC
Maximum continuous operating voltage UC(N-PE)
264V AC
Rated load current IL
40 A (Biconnect M4 fork cable pin 6 mm²)
63 A (TWIN cold press head 2 x 10 mm²)
Phoenix VAL-SEC-T2-3S-350/40-FM-2 class surge protector 2909635