Phoenix CB TM1 Series: Industrial Circuit Breakers - Selection Guide

Product Overview

The Phoenix CB TM1 Series consists of compact industrial circuit breakers designed for overcurrent and short-circuit protection in control cabinets and automation systems. Covering current ratings from 1A to 8A, with three core trip curve variants (SFB/M1/F1) and standardized "P" configuration, these breakers feature DIN rail mounting and robust construction. Ideal for protecting sensitive electronic components, control circuits, and small industrial loads, they ensure reliable fault protection while maintaining space-saving design for dense cabinet layouts.

Model Quick Reference Table

1. 1A Current Rating

Model No. Product Name Current Rating Trip Curve Key Features Application Scenarios
2800836 CB TM1 1A SFB P 1A SFB Standard "P" configuration Sensitive electronic circuits (low inrush current)
2800847 CB TM1 1A M1 P 1A M1 Standard "P" configuration General control circuits (moderate inrush)
2800858 CB TM1 1A F1 P 1A F1 Standard "P" configuration Fast-acting protection for precision electronics

2. 2A Current Rating

Model No. Product Name Current Rating Trip Curve Key Features Application Scenarios
2800837 CB TM1 2A SFB P 2A SFB Standard "P" configuration Low-power control modules and sensors
2800848 CB TM1 2A M1 P 2A M1 Standard "P" configuration Small relays and actuator control circuits
2800859 CB TM1 2A F1 P 2A F1 Standard "P" configuration Fast protection for delicate 2A-rated electronics

3. 3A Current Rating

Model No. Product Name Current Rating Trip Curve Key Features Application Scenarios
2800838 CB TM1 3A SFB P 3A SFB Standard "P" configuration Low-inrush 3A control circuits
2800849 CB TM1 3A M1 P 3A M1 Standard "P" configuration General-purpose 3A industrial load protection
2800860 CB TM1 3A F1 P 3A F1 Standard "P" configuration Fast-acting 3A electronic component protection

4. 4A Current Rating

Model No. Product Name Current Rating Trip Curve Key Features Application Scenarios
2800839 CB TM1 4A SFB P 4A SFB Standard "P" configuration Low-inrush 4A control systems
2800850 CB TM1 4A M1 P 4A M1 Standard "P" configuration Medium-load 4A actuator and relay circuits
2800861 CB TM1 4A F1 P 4A F1 Standard "P" configuration Fast protection for 4A precision electronics

5. 5A Current Rating

Model No. Product Name Current Rating Trip Curve Key Features Application Scenarios
2800840 CB TM1 5A SFB P 5A SFB Standard "P" configuration Low-inrush 5A industrial control circuits
2800851 CB TM1 5A M1 P 5A M1 Standard "P" configuration General 5A load protection (motors, pumps)
2800862 CB TM1 5A F1 P 5A F1 Standard "P" configuration Fast-acting 5A electronic equipment protection

6. 6A Current Rating

Model No. Product Name Current Rating Trip Curve Key Features Application Scenarios
2800841 CB TM1 6A SFB P 6A SFB Standard "P" configuration Low-inrush 6A control panels
2800852 CB TM1 6A M1 P 6A M1 Standard "P" configuration Medium-heavy 6A industrial load protection
2800863 CB TM1 6A F1 P 6A F1 Standard "P" configuration Fast protection for 6A sensitive electronics

7. 8A Current Rating

Model No. Product Name Current Rating Trip Curve Key Features Application Scenarios
2800842 CB TM1 8A SFB P 8A SFB Standard "P" configuration Low-inrush 8A control systems
2800853 CB TM1 8A M1 P 8A M1 Standard "P" configuration Heavy 8A load protection (industrial machinery)
2800864 CB TM1 8A F1 P 8A F1 Standard "P" configuration Fast-acting 8A electronic component protection

Core Technical Specifications (Universal)

Parameter Value Notes
Current Rating Range 1A~8A Model-dependent, covers small to medium loads
Trip Curves SFB (slow), M1 (medium), F1 (fast) Matches different load inrush characteristics
Operating Voltage Up to 400V AC / 250V DC Compatible with industrial power systems
Breaking Capacity 10kA (at 400V AC) High fault current handling capability
Mounting Type 35mm DIN rail (NS 35/7.5) Compact design (width: 17.5mm)
Protection Class IP20 (cabinet mounting) Dust-proof for industrial control cabinets
Operating Temperature -25℃~70℃ Adapts to harsh industrial environments
Connection Type Screw terminals Accepts 0.5~2.5mm² conductors
Certifications CE, UL, CSA, IEC 60898-1 Global industrial compliance
Reset Type Manual Easy fault recovery after tripping

Application Scenarios & Recommended Models

1. Sensitive Electronic Circuits (Low Inrush)

  • Requirement: 2A protection for precision sensors and control modules
  • Recommended Model: 2800837 (CB TM1 2A SFB P)
  • Key Reason: SFB slow trip curve avoids false tripping from minor current fluctuations

2. General-Purpose Industrial Loads

  • Requirement: 5A protection for relays, small motors, and pumps
  • Recommended Model: 2800851 (CB TM1 5A M1 P)
  • Key Reason: M1 medium trip curve balances inrush tolerance and fault protection

3. Fast-Acting Precision Equipment Protection

  • Requirement: 3A fast protection for delicate electronic components
  • Recommended Model: 2800860 (CB TM1 3A F1 P)
  • Key Reason: F1 fast trip curve quickly cuts off current to prevent component damage

4. Heavy Industrial Machinery (8A Loads)

  • Requirement: 8A protection for industrial machinery and heavy actuators
  • Recommended Model: 2800853 (CB TM1 8A M1 P)
  • Key Reason: M1 curve handles motor inrush; 10kA breaking capacity for severe faults

5. Low-Power Control Panels (1A~2A)

  • Requirement: 1A protection for control panel electronics
  • Recommended Model: 2800836 (CB TM1 1A SFB P)
  • Key Reason: Compact size, SFB curve for stable protection of low-power circuits

Core Advantages

  • Flexible Trip Curves: SFB/M1/F1 variants match diverse load inrush characteristics
  • Wide Current Coverage: 1A~8A range fits small to medium industrial loads
  • Compact Design: 17.5mm width saves control cabinet space for dense layouts
  • High Breaking Capacity: 10kA at 400V AC handles severe fault currents
  • Industrial-Grade Durability: -25℃~70℃ operating temperature, IP20 protection
  • Easy Installation: DIN rail mounting and screw terminals simplify deployment
  • Global Compliance: CE/UL/CSA certifications enable international use

Installation & Usage Notes

  • Trip Curve Selection: Choose SFB for low-inrush electronics, M1 for general loads, F1 for fast precision protection
  • Current Matching: Select rating slightly above normal operating current (avoid over-sizing)
  • Wiring Specifications: Use 0.5~2.5mm² conductors; strip wires to 8mm and tighten terminals to 0.5~0.8Nm
  • Mounting Spacing: Reserve ≥5mm between breakers for heat dissipation and operation space
  • Voltage Verification: Ensure compatibility with system voltage (AC/DC) before installation
  • Reset Operation: After tripping, identify and resolve fault cause before manual reset
  • Environmental Protection: Install in dry, dust-free control cabinets (IP20 protection); avoid moisture exposure

Phoenix CB TM1 Series: Industrial Circuit Breakers - Selection Guide

Created on:2025-11-21 13:52

News Dynamics

NEWS