Phoenix AXL E PB DI8 DO8 M12 6P-digital quantity module 2701497,Axioline E, digital quantity I/O equipment, PROFIBUS DP,M12 connector, digital input: 8,24V DC, connection technology: 4 wires, digital output: 8,24V DC, connection technology: 3 wires, plastic shell, protection level: IP65/IP67
width |
60mm |
height |
185mm |
depth |
30.5mm |
hole spacing |
198.5mm |
Notes on dimensional data |
height is 212mm including the retaining clip. |
Application Description |
Application Description |
for industrial applications only |
Use Restrictions |
EMC Description |
EMC: Class A products, see the manufacturer's declaration in the download area |
Shell Material |
Pocan® |
color |
dark gray |
PROFIBUS DP |
Channels |
2 |
Connection Mode |
M12 Connector |
Connection Method Considerations |
B coding |
Bits |
5 |
transmission speed |
9,6 kBit/s ... 12 MBit/s (automatic baud rate detection) |
transmission principle |
PROFIBUS DP Compatible Copper Cable |
Address Space Allocation |
1 ... 126, adjustable |
PROFIBUS DP |
Device Type |
PROFIBUS from machine |
System Specific Protocol |
PROFIBUS Transfer Protocol DP V1 |
Module |
Hex ID Encoding |
0E5D |
Input Address Area |
8. |
Output Address Area |
8. |
digital quantity: |
Enter Name |
Digital Input |
Input Description |
EN 61131-2 types 1 and 3 |
Input Quantity |
8 |
Cable Length |
max. 30 m (to sensor) |
Connection Mode |
M12 pin plug connector, dual channel slot |
connection system |
4 lines |
input voltage range, "0" signal |
0V DC ... 5V DC |
input voltage range, "1" signal |
11V DC ... 30V DC |
Rated input voltage UIN |
24V DC |
Rated input current UIN |
Typical 3 mA |
sensor current per channel |
typical value 75 mA (from US) |
Total sensor current |
Maximum 0.6 A (per device) |
input filter time |
< 1000 µs |
protection circuit |
overload protection, sensor power short circuit protection |
digital quantity: |
Output Name |
Digital Output |
Connection Mode |
M12 pin plug connector, dual channel slot |
connection system |
3 lines |
outputs |
8 |
protection circuit |
output; Yes |
output voltage |
24V DC |
Voltage limitation due to current interruption |
-28V ... -17V |
the maximum output current per channel |
500 mA |
Rated output voltage |
24V DC (from voltage UA) |
Output Voltage Range |
18V DC ... 31.2V DC |
is disconnected |
max. 1V |
is disconnected |
max. 20 & micro;A |
load rating, inductive |
12 VA (1.2 H,48 Ω, rated voltage) |
Rated load, resistive |
12W (48Ω, rated voltage) |
Switching frequency |
maximum 5500 per second (load current not less than 50 mA) |
max. 1 second (with inductive load) |
reverse voltage against short pulses |
Prevent reverse voltage |
overload behavior |
automatic restart |
signal delay |
maximum 150 & micro;s (at power-up) |
maximum 200 & micro;s (when switched off) |
overcurrent shutdown |
Minimum 0.7 A |