Phoenix TRIO-PS-2G/1AC/24DC/3/C2LPS-power supply 2903147, TRIO POWER power supply with in-line connection, suitable for DIN rail installation, primary switch mode, input: single phase, output: 24V DC/3 A C2LPS
AC operation
Network Type
star network
Rated input voltage range
100V AC ... 240V AC
Input Voltage Range
100V AC ... 240V AC -15 % ... +10%
AC input voltage range
85V AC ... 264V AC
maximum dielectric strength
≤ 300V AC 15 s
National Grid Typical Voltage
120V AC
230V AC
Supply Voltage
AC/DC
Impulse current
≤ 15 A (typical)
impulse current integral (I2t)
< 0.26 A2s
Surge current limit
Typical 15 A (after 1 ms)
AC frequency range
50Hz ... 60Hz ± 10%
grid buffer time
Typical 10 ms (120V AC)
Typical 20 ms (230V AC)
power consumption
1.4 A (100V AC)
1 A (120V AC)
0.6 A (230V AC)
0.7 A (240V AC)
Rated power consumption
157.7 VA
protection circuit
transient surge protection; varistor
power factor (cos phi)
0.52
Typical Response Time
< 1 s
input fuse
6.3 A (built-in (equipment protection))
recommend use
6 A ... 16 A (characteristics B, C, D, K)
PE discharge current
< 0.25 mA
DC operation
Rated input voltage range
110V DC ... 250V DC
Input Voltage Range
99V DC ... 275V DC
Supply Voltage
AC/DC
grid buffer time
> 20 ms (230V AC)
power consumption
0.8 A (110V DC)
0.3 A (250V DC)
efficiency
> 89% (230V AC and rated)
output characteristics
U/ I with dynamic load reserve
Rated output voltage
24V DC ±1%
output voltage (USet) setting range
24V DC ... 28V DC (> 24V DC, stable capacity limit)