Phoenix EMD-SL-V-UV-300-monitoring relay 2866035, monitoring relay for 1-phase voltage monitoring of 0…300V AC/DC, undervoltage, power supply voltage can be selected by the power module, 1 changeover contact
Product Type
Voltage monitoring relay
Mode of operation
100% operating factor
mechanical life
approx. 2x 107times
insulation characteristics
insulation
Foundation Isolation
Overvoltage Category
III
pollution level
2
service life, electrical
2x 105times, resistive load 1000 VA
Main Power Type
single phase
Rated insulation voltage
300V
Rated overvoltage
4 kV
power supply
Supply Voltage Range
24V AC ... 230V AC (see Power module)
24V DC (see Power module)
Rated power consumption
2 VA (1.5 W)
Enter Name
Measurement Input
measured value
AC sine (48 ... 63Hz)
protection
≤ 20 A
Input Voltage Range
0V ... 30V AC/DC (Terminal blocks: U1 and GND)
0V ... 60V AC/DC (Terminal blocks: U2 and GND)
0V ... 300V AC/DC (Terminal blocks: U3 and GND)
Maximum input voltage
100Vrms(Terminals: U1 and GND)
150Vrms(Terminals: U2 and GND)
440Vrms(Terminals: U3 and GND)
input voltage
47 kΩ (Terminal blocks: U1 and GND)
100 kΩ (terminal blocks: U2 and GND)
470 kΩ (Terminal blocks: U3 and GND)
Frequency Range
50Hz ... 60Hz
maximum temperature coefficient
< 0.1 %/K
Response Delay Setting Range
0.2 s ... 10 s
Minimum setting range
5 % ... 95 % (UN)
Maximum setting range
10 % ... 100 % (UN)
Function
undervoltage
basic accuracy
± 5% (final value)
Setting Accuracy
≤ 5% (final value)
repeat accuracy
≤ 2%
Recovery Time
500 ms
switching
Contact Type
1 floating transfer contact
maximum switching voltage
250V AC (according to IEC 60664-1)
Maximum power rating (resistive load)
750 VA (3 A/250V AC, module arrangement, spacing ≤ 5mm)
1250 VA (5A/250V AC, modules not arranged, spacing ≥ 5mm)