Phoenix TRIO-PS-2G/1AC/24DC/5-power supply 2903148, TRIO POWER power supply with in-line connection, suitable for DIN rail installation, primary switching mode, input: single phase, output: 24V DC/5 A

AC operation
Network Type star network
Rated input voltage range 100V AC ... 240V AC
Input Voltage Range 100V AC ... 240V AC -15 % ... +10%
AC input voltage range 85V AC ... 264V AC
maximum dielectric strength ≤ 300V AC 15 s
National Grid Typical Voltage 120V AC
230V AC
Supply Voltage AC/DC
Impulse current ≤ 16 A (typical)
impulse current integral (I2t) < 0.6 A2s
Surge current limit Typical 16 A (after 1 ms)
AC frequency range 50Hz ... 60Hz ± 10%
grid buffer time Typical 20 ms (120V AC)
Typical 100 ms (230V AC)
power consumption 2.2 A (100V AC)
1.9 A (120V AC)
1.1 A (230V AC)
1.1 A (240V AC)
Rated power consumption 272 VA
protection circuit transient surge protection; varistor
power factor (cos phi) 0.5
Typical Response Time < 1 s
input fuse 6.3 A (built-in (equipment protection))
recommend use 6 A ... 16 A (characteristics B, C, D, K)
PE discharge current < 0.25 mA
DC operation
Rated input voltage range 110V DC ... 250V DC
Input Voltage Range 99V DC ... 275V DC
turn-on voltage ≥ 88V DC
Shutdown Voltage < 60V DC
Supply Voltage AC/DC
grid buffer time > 100 ms (230V AC)
power consumption 1.4 A (110V DC)
0.6 A (250V DC)

efficiency > 90% (230V AC and rated)
output characteristics U/ I with dynamic load reserve
Rated output voltage 24V DC ±1%
output voltage (USet) setting range 24V DC ... 28V DC (> 24V DC, stable capacity limit)
Rated output current (IN) 5 A
Dynamic Boost (IDyn.Boost) 7.5 A (5 s)
Attenuation > 60°C ... 70°C (2.5 %/K)
feedback voltage resistance ≤ 35V DC
output ≤ 30V DC
control deviation <1% (load change, static 10%... 90%)
<3% (dynamic load change 10%... 90%, 10Hz)
< 0.1 % (input voltage variation is ± 10 %)
residual wave < 50 mVSS(rated value)
output power 120W
180W
maximum no-load power consumption < 1W
Maximum rated load power loss < 16W
rise time ≤ 12 ms (UOUT(10%... 90%))
and connect Yes, for redundancy and increased capacity
Concatenation is
signal: DC OK
maximum switching voltage 30V AC/DC
Continuous load current 100 mA
2903147

Phoenix TRIO-PS-2G/1AC/24DC/5-Power 2903148

Product Center

PRODUCT CENTER