Phoenix TRIO-PS-2G/3AC/24DC/5-power supply 2903153, TRIO POWER switching power supply with in-line connection, suitable for DIN rail installation, three-phase input, output: 24V DC/5 A
AC operation
Network Type
star network
Rated input voltage range
3x 400V AC ... 500V AC
2x 400V AC ... 500V AC
Input Voltage Range
3x 400V AC ... 500V AC -20 % ... +15%
2x 400V AC ... 500V AC -10 % ... +15%
AC input voltage range
3x 320V AC ... 575V AC
National Grid Typical Voltage
3x 400V AC
3x 480V AC
Supply Voltage
AC
Impulse current
≤ 22 A (typical)
impulse current integral (I2t)
≤ 0.25 A2s
AC frequency range
50Hz ... 60Hz
grid buffer time
Typical 20 ms (400V AC)
Typical 20 ms (500V AC)
power consumption
3x 0.4 A (400V AC)
3x 0.3 A (500V AC)
2x 0.6 A (400V AC)
2x 0.5 A (500V AC)
Rated power consumption
243.6 VA
protection circuit
transient surge protection; varistor
power factor (cos phi)
0.55
Typical Response Time
< 1 s
input fuse
3.15 A (built-in (device protection) slow fuse)
recommend use
6 A ... 16 A (characteristics B, C, D, K)
PE discharge current
< 0.25 mA
< (550V AC, 60 Hz)
efficiency
> 91% (at 400V AC and rated)
output characteristics
U/ I with dynamic load reserve
Rated output voltage
24V DC ±1%
output voltage (USet) setting range
24V DC ... 28V DC (> 24V DC, stable capacity limit)
Rated output current (IN)
5 A
Dynamic Boost (IDyn.Boost)
7.5 A (5 s)
Attenuation
> 60°C ... 70°C (2.5 %/K)
output
≤ 30V DC
control deviation
<1% (load change, static 10%... 90%)
<3% (dynamic load change 10%... 90%, 10Hz)
< 0.1 % (input voltage variation is ± 10 %)
residual wave
≤ 20 mVSS
Short-circuit protection
is
Anti-aircraft turn
is
output power
120W
180W
maximum no-load power consumption
< 1W (400V AC)
Maximum rated load power loss
< 12W (480V AC)
rise time
≤ 120 ms (UOUT(10%... 90%))
and connect
Yes, for redundancy and increased capacity
Concatenation
is
signal: DC OK
Continuous load current
100 mA
signal relay 13/14
Default (Value)
closed
digital quantity
30V AC 30V DC 100 mA
Input
Connection Mode
in-line connection
Minimum cross section of rigid conductor
0.2 mm²
Maximum cross section of rigid conductor
4 mm²
flexible lead
0.2 mm²
Flexible lead maximum cross section
2.5 mm²
Single conductor/terminal point, flexible, with sleeve, minimum
0.2 mm²
Single conductor/connection point, flexible, with sleeve, maximum