Phoenix ST 6-PE-ground terminal 3031500, ground terminal, connection quantity: 2, wiring method: pull-back spring connection, first layer, cross section: 0.2 mm2 -10mm2, installation method: NS 35/7,5, NS 35/15, color: yellow-green
Product Type |
Ground terminal |
Application areas |
railway industry |
Mechanical Engineering |
Plant Engineering |
Process Industry |
connection quantity |
2 |
Rows |
1 |
insulation characteristics |
Overvoltage Category |
III |
pollution level |
3 |
Rated surge voltage |
8 kV |
rated conditions |
1.31W |
the number of connections per layer |
2 |
Rated cross section |
6 mm² |
first layer |
Considerations |
Note the ampacity of the DIN rail. |
stripping length |
12mm |
plug gauge |
A5 |
connection meets standards |
IEC 60947-7-2 |
Rigid conductor cross section |
0.2 mm² ... 10 mm² |
cross section AWG |
24 ... 8 (as amended by IEC standards) |
Flexible Wire Cross Section |
0.2 mm² ... 6 mm² |
WIRE CROSS SECTION, FLEXIBLE [AWG] |
24 ... 10 (as amended by IEC standards) |
Flexible conductor cross-section (sleeve without plastic insulation) |
0.25 mm² ... 6 mm² |
flexible conductor cross-section (sleeve with plastic insulating tube) |
0.25 mm² ... 6 mm² |
rated parameters (ATEX/IECEx) |
Identification |
II 2 GD Ex eb IIC Gb |
Operating temperature range |
-60°C ... 85°C |
Ex Certified Accessories |
3030433 D-ST 6 |
1204520 SZF 2-0,8X4,0 |
3022276 CLIPFIX 35-5 |
3022218 CLIPFIX 35 |
Output |
(Permanent) |
Ex Connection Data Overview |
Rated cross section |
6 mm² |
Rated wiring capacity AWG |
10 |
Rigid Wiring Capacity |
0.2 mm² ... 10 mm² |
Wiring capacity AWG |
24 ... 8 |
flexible wiring capacity |
0.2 mm² ... 6 mm² |
Wiring capacity AWG |
24 ... 10 |
width |
8.2mm |
End plate width |
2.2mm |
height |
69.5mm |
NS 35/7,5 depth |
43.5mm |
NS 35/15 Depth |
51mm |
color |
green and yellow |
flame retardant rating, according to UL 94 |
V0 |
Insulation Material Group |
I |
insulation material |
PA |
Application of Static Insulation Materials at Low Temperature |
-60°C |
Insulation Relative Temperature Index (Electrical, UL 746 B) |
130°C |
railway vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
Fire protection of railway vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
railway vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
Fire protection of railway vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |
Surface Flammability NFPA 130 (ASTM E 162) |
through |
Smoke specific optical density NFPA 130 (ASTM E 662) |
through |
Smoke Toxicity NFPA 130 (SMP 800C) |
through |