Phoenix IB IL 24 LPSDO 8 V2-PAC-safety module 2700606, safety-related digital output module, IP20 protection level, used in SafetyBridge systems. The module has 4 safe digital outputs for 2 channels, or 8 safe digital outputs for 1 channel
width
48.8mm
height
119.8mm
depth
71.5mm
Notes on dimensional data
Shell Size
Description
Application Description
Application Description
for industrial applications only
Interface
Inline Local Bus
Channels
2
Connection Mode
Inline data span block
transmission speed
500 kBit/s / 2 MBit/s (switchable)
System Properties
SafetyBridge Properties
and I/O module connections
max. 5 (Secure Digital I/O Module)
Logical Storage
24 kilobytes kByte
Module
ID Code (dec.)
171
Hex ID Encoding
AB
Length Encoding (Hexadecimal)
18
length encoding (decimal)
24
Process Data Channel
48 Byte
Input Address Area
48 Byte ((operation mode: SafetyBridge 24 characters))
Output Address Area
48 Byte ((operation mode: SafetyBridge 24 characters))
Register Length
48 Byte
the required parameter data
1 Byte ((operation mode: SafetyBridge 24 characters))
5 Byte ((operation mode: SafetyBridge 24 characters))
Output Data
digital quantity:
Output Name
Digital Output
Connection Mode
pull-back spring connection
connection system
2,3,4 lines
outputs
4 (for dual channel distribution)
8 (for single channel distribution)
8
protection circuit
output
output voltage
24V DC (US - 1 V)
output current
max. 6 A (total current of all outputs,-25°C ... 50°C)
max. 4 A (total current of all outputs,>-50°C ... 55°C)
Maximum output current per group
3 A
the maximum output current per channel
2 A
Rated output voltage
24V DC
load rating, inductive
See Safety Data
rated load, indicator light
See Safety Data
Rated load, resistive
See Safety Data
Inductor overload action
output may be corrupted
Product Properties
Product Type
I/O components
Product Series
Inline
Application
Functional Safety
SafetyBridge Technology
type
Module
diagnostic information
Digital output short circuit or overload fault information is displayed in the form of diagnostic codes (bus) via LEDs on the motor
Electrical characteristics
rated conditions
144W
transmission medium
copper cable
potential: communication power supply (UL )
supply voltage
7.5V DC (see safety data)
current consumption
maximum 230 mA (see safety data)