Phoenix AXL F BK ETH-bus coupler 2688459,Axioline F, bus coupler, Modbus/TCP(UDP),RJ45 female connector, local bus transmission rate: 100 Mbps, protection level: IP20, including bus base module and Axioline connector
width | 45mm |
height | 126.1mm |
depth | 74mm |
Notes on dimensional data | using TH 35-7.5 rails (as EN60715). |
Application Description | |
Application Description | for industrial applications only |
Modbus/TCP (UDP) | |
interfaces | 2 |
Connection Mode | RJ45 female connector |
Connection Method Considerations | adaptive and self-crossover |
transmission speed | 10/100 MBit/s (half-duplex or full-duplex mode (automatic detection, can be adjusted manually)) |
transmission principle | Ethernet RJ45 Twisted Pair |
Axioline F Local Bus | |
interfaces | 1 |
Connection Mode | bus base module |
transmission speed | 100 Mbps |
Services | |
interfaces | 1 |
Connection Mode | USB Type-C (as of HW 05) |
Micro USB Type B (up to HW04) |
System Limitations | |
maximum 63 (per station) | |
the number of local bus devices that can be connected | maximum 63 |
Product Type | I/O components |
product series | Axioline F |
type | Modular structure |
Installation position | any position (observe temperature attenuation) |
Scope of supply | includes bus base module and Axioline connector |
insulation characteristics | |
Overvoltage Category | II (IEC 60664-1,EN 60664-1) |
pollution level | 2 (IEC 60664-1,EN 60664-1) |
rated conditions | 4W |
potential: communication power ULfeed (Axioline F local bus UBusis powered by UL) | |
supply voltage | 24V DC |
Supply Voltage Range | 19.2V DC ... 30V DC (includes all tolerances, including ripple) |
current consumption | maximum 583 mA (UBusis 2.0 A,UL= 24V, max. HW 04) |
maximum 670 mA (UBusis 2.5 A,UL= 24V,HW 05 or higher) | |
protection circuit | surge protection; electronic |
polarity protection; electronic | |
potential: Axioline F local bus (UBus) power supply | |
supply voltage | 5V DC (via bus base module) |
Power | 2 A max (up to HW04) |
Maximum 2.5 A (from HW 05) | |
electrical isolation/isolation for voltage range | |
test voltage: Ethernet interface 1/Ethernet interface 2 | 1500V AC, 50 Hz, 1 min |
test voltage: Ethernet interface 1/24V communication voltage (UL) Feed | 1500V AC, 50 Hz, 1 min |
test voltage: Ethernet interface 2/24V communication voltage (UL) Feed | 1500V AC, 50 Hz, 1 min |
test voltage: Ethernet interface 1/function ground | 1500V AC, 50 Hz, 1 min |
test voltage: Ethernet interface 2/function ground | 1500V AC, 50 Hz, 1 min |
test voltage: 24V communication voltage (UL) Feed/Functional Grounding | 500V AC, 50 Hz, 1 min |
connection technology | |
Connection Name | Axioline F plug |
Connection Method Considerations | Please note the information on conductor cross-sections in the "Axioline F: System and Installation" user manual. |
Wire Connection | |
Connection Mode | in-line connection |
Rigid conductor cross section | 0.2 mm² ... 1.5 mm² |
Flexible Wire Cross Section | 0.2 mm² ... 1.5 mm² |
Attachable Guide Cross Section AWG | 24 ... 16 |
stripping length | 8mm |