Phoenix PSR-SCP- 24UC/URM/5X1/1X2-coupling relay 2981952, safety coupling relay with forced guide contacts, 5 normally open contacts, 1 normally closed contact, plug-in screw terminal block, width: 22.5mm
Application Description | |
Application Description | for industrial applications only |
Product Type | coupling relay |
product series | PSRclassic |
Application | Safety Shutdown |
high requirements | |
low requirements | |
control | Single and Dual Channel |
mechanical life | 10x 106Switch Times |
Relay Model | Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3 |
restart time | < 1 s (start-up time) |
rated conditions | 8.56W (in UB= 26.4V DC,US= 24 V, IS= 47 mA,n = 1, IL² = 72 A²,Rcontact= When 0.1,) |
Rated operating mode | 100% Eligible |
Electrical clearance and creepage distance between power supply circuits | |
Rated insulation voltage | 250V |
250V | |
rated overvoltage/insulation | 4kV/base safety isolation (between A1/A2, 53/54, 71/72 and 13/14, 23/24, 33/34, 43/44, using 6kV enhanced safety isolation). |
Overview | |
Rated control circuit supply voltage US | 24V AC/DC -15 % / +10% |
US | Typical 1.2W |
Rated control supply current IS | Typical 47 mA |
Input Voltage Range | 20.4V AC/DC ... 26.4V AC/DC |
Impulse current | Typical 350 mA DC (& Delta;t < 1 & micro;s Us) |
Typical 350 mA AC (& Delta;t = 2 ms Us) | |
Typical startup time (Us) | Typical 20 ms (when controlled via A1) |
Typical release time | Typical 20 ms (when controlled via A1) |
Recovery Time | < 500 ms |
Maximum switching frequency | 0.5Hz |
protection circuit | Surge protection; Varistor |
Operating voltage display | 1 x LED (green) |
Contact Type | 5 normally open safety contact outputs |
1 feedback loop | |
Contact Material | AgSnO2 |
maximum switching voltage | 230V AC/DC (note load curve) |
Minimum Switching Voltage | 5V AC/DC |
limit continuous current | 6 A (N/O contact) |
6 A (normally closed contact) | |
Maximum starting current | 6 A |
Minimum impulse current | 10 mA |
the square of the total current value | 72 A2 |
Maximum power rating (resistive load) | 144W (normally open contact, 24V DC, & tau; = 0 ms) |
288W (normally open contact, 48V DC, & tau; = 0 ms) | |
240W (normally open contact, 60V DC, & tau; = 0 ms) | |
110W (normally open contact, 110V DC, & tau; = 0 ms) | |
88W (normally open contact, 220V DC, & tau; = 0 ms) | |
1380 VA (normally open contact, 230V AC, & tau; = 0 ms) | |
Maximum power rating (inductive load) | 42W (normally open contact, 24V DC, & tau; = 40 ms) |
42W (normally open contact, 48V DC, & tau; = 40 ms) | |
42W (normally open contact, 60V DC, & tau; = 40 ms) | |
42W (normally open contact, 110V DC, & tau; = 40 ms) | |
42W (normally open contact, 220V DC, & tau; = 40 ms) | |
On-Off Capacity | 50 mW minimum |
switching capacity according to IEC 60947-5-1 | 3 A (24V (DC13)) |
3 A (230V (AC 15)) | |
on-off capacity (360/h cycle) | 4 A (24V (DC13)) |
4 A (230V (AC15)) | |
output fuse | 10 A gL/gG (N/O contact) |
4 A gL/gG (normally open contact for low demand applications) | |
6 A gL/gG (normally closed contact) |