movement direction |
Line-Line & Line-Ground/Shield |
Maximum continuous voltage Uc |
185V DC |
130V AC |
Rated current |
≤ 380 mA (25 °C) |
UC, the effective working current IC |
≤ 6 µA |
Residual Flow IPE |
≤ 4 µA |
Nominal discharge current In(8/20) & micro;s (core-core) |
≤ 5 kA |
Rated discharge current In(8/20)& micro;s (core-ground) |
≤ 5 kA |
Total discharge current Itotal(8/20) µs |
10 kA |
rated power pulse current lan (1000)& micro;s (core-core) |
100 A |
rated power pulse current lan (1000)& micro;s (core-ground) |
100 A |
rated power pulse current lan (700)& micro;s (core-core) |
150 A |
rated power pulse current lan (700)& micro;s (core-ground) |
150 A |
Output voltage limit 1 kV/& micro;s (core-core) static |
≤ 250V |
Output voltage limit 1 kV/& micro;s (core-ground) static |
≤ 250V |
Residual voltage ln,(wire-wire) |
≤ 120V |
Residual voltage ln,(wire-ground) |
≤ 120V |
voltage protection level Up(core-core) |
≤ 250V (B2 - 4 kV / 100 A) |
≤ 250V (C1 - 1 kV / 500 A) |
≤ 250V (C2 - 10 kV / 5 kA) |
voltage protection level Up(line-ground) |
≤ 250V (B2 - 4 kV / 100 A) |
≤ 250V (C1 - 1 kV / 500 A) |
≤ 250V (C2 - 10 kV / 5 kA) |
response time tA(core-core) |
≤ 100 ns |
response time tA (core-ground) |
≤ 100 ns |
input attenuation AE, symmetric. |
Typical 0.5 dB (≤ 5 MHz / 100 Ω) |
Typical 0.3 dB (≤ 8 MHz/150 Ω) |
Typical 0.3 dB (≤ 2.5 MHz / 600 Ω) |
cut-off frequency fg(3 dB),100 Ω symmetric system |
Typical 50 MHz |
capacitance (core-core) |
Typical 20 pF (f = 1 MHz / VR = 0V) |
capacitance (core-ground) |
Typical 20 pF (f = 1 MHz / VR = 0V) |
the resistance of each path |
3.3 Ω 10% |
Surge protection fault alarm |
None |
Impact tolerance (line-line) |
B2 - 4 kV / 100 A |
C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA |
Impact resistance (line-ground) |
B2 - 4 kV / 100 A |
C1 - 1 kV / 500 A |
C2 - 10 kV / 5 kA |
D1 - 1 kA |