Phoenix PT 3-PB-ST-Surge Protector-Plug-in 2858030, surge protection plug, installed on the base, used for regular mode voltage coarse/fine protection of 2 floating ground signal lines in IT system, And common mode voltage ground coarse protection.
Product Type | Information Technology |
Product Series | PLUGTRAB PT |
IEC Category | C1 |
C2 | |
C3 | |
D1 | |
VDE requirement level | C1 |
C2 | |
C3 | |
D1 | |
type | needle type |
Bits | 2 |
can test protectors using the CHECKMASTER software tests: | |
line pairs per module | 3 |
insulation characteristics | |
Overvoltage Category | III |
pollution level | 2 |
Rated voltage UN | 5V DC |
Connection Mode | screw connection (connection to the base) |
thread | M3 |
Tightening torque | 0.8 Nm |
Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
Rigid conductor cross section | 0.2 mm² ... 4 mm² |
Attachable Guide Cross Section AWG | 24 ... 12 |
Dimensional drawing | |
width | 17.7mm |
height | 45mm |
depth | 52mm |
Horizontal stitch pitch | 1 Partition |
full module width | 17.7mm |
Full module height | 90mm |
full module depth | 65.5mm |
color | black (RAL 9005) |
flame retardant rating, according to UL 94 | V-0 |
Shell Material | PA |
Mechanical parameters | |
Open Side Panel | No |
movement direction | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Maximum continuous voltage Uc | 5.2V DC |
3.6V AC | |
Rated current | 450 mA (45°C) |
UC, the effective working current IC | ≤ 300 µA |
Residual Flow IPE | ≤ 300 & micro;A (with PT 1X2-BE) |
≤ 1 & micro;A (with PT 1X2 F-BE) | |
Rated discharge current In(8/20)& micro;s (core-ground) | 10 kA |
pulse discharge current Iimp(10/350) µs | 2.5 kA |
Total discharge current Itotal(8/20) µs | 20 kA |
Maximum discharge current Imax(8/20) & micro;s (core-core) | 10 kA |
Maximum discharge current Imax(8/20) & micro;s (core-ground) | 10 kA |
rated power pulse current lan (1000)& micro;s (core-core) | 90 A |
Output voltage limit 1 kV/& micro;s (core-to-core) peak | ≤ 55V |
Output voltage limit 1 kV/& micro;s (core-ground) peak | ≤ 55V (with PT 1X2-BE) |
≤ 700V (with PT 1X2 F-BE) | |
Output voltage limit 1 kV/& micro;s (core-core) static | ≤ 15V |
Output voltage limit 1 kV/& micro;s (core-ground) static | ≤ 15V |
≤ 30V (with PT 1X2 F-BE) | |
residual voltage ln,(wire-wire) | ≤ 15V |
residual voltage ln,(wire-ground) | ≤ 30V (with PT 1X2-BE) |
In(line-signal ground) | ≤ 15V (with PT 1X2-BE) |