Phoenix MACX MCR-EX-SL-RPSS-2I-2I-Feeder Isolator 2865382, Intriguently Safe Measurement Transmitter Power Supply, 2 Channels; HART Transparent. It can supply power to the 2-wire measuring transmitter, and 4 mA... The 20 mA signal is transmitted from the explosion-proof area to the safe area. 5-way galvanic isolation, screw connection, max. SIL 3,PL.

Product Type Feeder Isolator
Product Series MACX Analog
Application Analog Input
Channels 2
Model Ex I Isolation Amplifier with SIL and PL Functional Safety

electrical isolation 5 End Isolation
galvanic isolation between input and output is
Signal Transmission Behavior In = Out
step response (10-90%) < 1.3 ms (for jumpers 4 mA ... 20 mA)
maximum temperature coefficient < 0.01 %/K
Maximum transmission error < 0.1 % (final value 20 mA)
Typical transmission error < 0.05 % (final value 20 mA)
electrical isolation
Overvoltage Category II
pollution level 2
electrically isolated input/output, power supply IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
Test Voltage 2.5 kV AC (50 Hz, 60 s)
insulation security isolation
electrical isolation input/output IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 265Vrms
galvanically isolated input/power supply IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 265Vrms
galvanically isolated output 1/output 2/power supply
Test Voltage 1.5 kV AC (50 Hz, 60 s)
power supply
Rated supply voltage 24V DC -20 % ... +25%
Supply Voltage Range 19.2V DC ... 30V DC
Maximum current consumption < 100 mA (24V DC / 20 mA)
power consumption < 1.4W (24V DC / 20 mA)
power consumption ≤ 2.4W