Phoenix MACX MCR-EX-SL-SD-21-60-LP-SP-electromagnetic driver 2924100,Ex I electromagnetic driver. Intra-safe control of Ex I solenoid valves, alarm modules or LEDs installed in the Ex area. Current limit 58 mA. For the highest IIB group gases, loop powered, electrically isolated, SIL 3. Plug-type interface.
| Product Type | Electromagnetic driver |
| Product Series | MACX Analog |
| Channels | 1 |
| Model | Ex I Isolation Amplifier with SIL Functional Safety |
| compatible valve | ASCO Coil 302 (12 V) |
| ASCO Coil 302 (24 V) | |
| Bürkert Coil AC 10 standard | |
| Bürkert Coil AC 10 high resistance | |
| FESTO Coil MFH-...IA-SA-EX GBXE022AIAD03 | |
| FESTO Coil (J)MFH-...BIA-SA-EX GBXE022AIAD03 | |
| Norgren Herion Coil 2050 | |
| Norgren Herion Coil 2051 | |
| Norgren Herion Coil 2052 | |
| Norgren Herion Coil 2053 | |
| Parker Coil VZ95 482160.01 EEx ia IIB T6 | |
| Considerations | This is a summary of possible valves and solenoid actuators. |
| electrical isolation | 2 road isolation |
| maximum temperature coefficient | 0.01 %/K |
| electrical isolation | |
| Test Voltage | 2.5 kV AC (50 Hz, 60 s) |
| Overvoltage Category | II |
| pollution level | 2 |
| galvanically isolated output/input IEC/EN 60079-11 | |
| Standards/Regulations | IEC/EN 60079-11 |
| Rated insulation voltage | 375VPP |
| galvanically isolated output/input IEC/EN 61010-1 | |
| Standards/Regulations | IEC/EN 61010-1 |
| Rated insulation voltage | 300Vrms |
| insulation | security isolation |
| power supply | |
| Supply Voltage Range | loop power supply, no external power supply required |
| power consumption | < 1.325W |
| signals: voltage | |
| Input Number | 1 |
| voltage input signal | 19.2V DC ... 30V DC (24V DC,-20 % ... +25 %) |
| Maximum current input signal | 95 mA (Ue= 24V DC) |
| signals: voltage | |
| Output Description | this safety |
| outputs | 1 |
| output voltage | ≥ 12.9V DC (58 mA) |
| Current Limit | > 58 mA |
| response time | < 20 ms |
| No-load voltage | > 21.9V DC |
| Short-circuit protection | is |