Phoenix MACX MCR-IDS-I-I-output isolation amplifier 2908063, output signal isolation transmitter, HART transparent. Isolate and transmit the 0/4 mA ... 20 mA signal to the load in the safe area. 3-terminal electrical isolation, line fault detection (can be turned off by DIP switch), SIL 2 (SC3) in accordance with IEC 61508, screw connection.

Product Type Output Isolation Amplifier
Product Series MACX Analog
Channels 1
Model Isolation Amplifier with SIL Functional Safety
configuration DIP switch

Function
configuration DIP switch

electrical isolation 3 End Isolation
signal transmission behavior In = Out
step response (10-90%) < 140 & micro;s (for jumpers 4 mA ... 20 mA)
maximum temperature coefficient 0.01 %/K
temperature coefficient, typical ≤ 0.005 %/K
Maximum transmission error 0.1 % (final value 20 mA)
Typical transmission error ≤ 0.05 % (final value 20 mA)
electrical isolation
Overvoltage Category II
pollution level 2
electrical isolation input/output IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
Test Voltage 2.5 kV AC (50 Hz, 60 s)
insulation security isolation
electrically isolated input/power supply IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 50Vrms
Test Voltage 1.5 kV AC (50 Hz, 60 s)
insulation Foundation Isolation
galvanically isolated output/power supply IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
Test Voltage 2.5 kV AC (50 Hz, 60 s)
insulation security isolation
power supply
Rated supply voltage 24V DC -20 % ... +25%
Supply Voltage Range 19.2V DC ... 30V DC
Maximum current consumption < 45 mA (24V DC / 20 mA)
power consumption < 0.8W (24V DC / 20 mA)
power consumption ≤ 1.1W (24V DC / 20 mA)

signals: current
current input signal 0 mA ... 20 mA (function (short-circuit detection off))
0.2 mA ... 20 mA (function (short-circuit detection start))
4 mA ... 20 mA (safe)
0 mA ... 24 mA (undervoltage/overvoltage signal range)
input current ≤ 30 mA
input impedance > 1 MΩ (in case of line fault)
Line Fault Detection > 0.2 mA (Input Current Response Threshold)
voltage drop < 2.4V (at 20 mA)