Phoenix MACX MCR-RTD-I-SP-temperature measurement transmitter 1050201, temperature measurement transmitter, can convert the signal from the resistance thermometer and resistance into an analog 0/4 mA - 20 mA signal. Freely programmable, push-in pluggable interface, SIL,3-terminal isolation, standard configuration.
Product Type
temperature measurement transmitter
Product Series
MACX Analog
Application
temperature
Channels
1
Model
Isolation Amplifier with SIL Functional Safety
configuration
Software
System Properties
Function
configuration
Software
Electrical characteristics
electrical isolation
3 End Isolation
galvanic isolation between input and output
is
step response (0-99%)
≤ 1.7 s
temperature coefficient, typical
0.01 %/K
Typical transmission error
0.1 % (e. g. for Pt 100,300 K range, 4 ... 20 mA)
electrical isolation
Test Voltage
2.5 kV AC (50 Hz, 60 s)
Overvoltage Category
II
pollution level
2
Electrically isolated input/output/power supply IEC/EN 61010-1
Standards/Regulations
IEC/EN 61010-1
Rated insulation voltage
300Vrms
insulation
security isolation
electrical isolation input/output IEC/EN 60079-11
Standards/Regulations
IEC/EN 60079-11
Rated insulation voltage
375VPP
galvanically isolated input/power supply IEC/EN 60079-11
Standards/Regulations
IEC/EN 60079-11
Rated insulation voltage
375VPP
power supply
Rated supply voltage
24V DC -20 % ... +25%
Supply Voltage Range
19.2V DC ... 30V DC
power consumption
≤ 0.76W
power consumption
≤ 1W
input data
signal
Input Number
1
measurement
Available Sensor Types (RTDs)
Pt, Ni, Cu sensors: 2, 3, 4 wires
Temperature measurement range
-200°C ... 850°C (range depends on sensor type)
Linear resistance measuring range
0 Ω ... 50 kΩ
potentiometer, resistance range
0 Ω ... 50 kΩ
Allowable Total Conductor Resistance
50 Ω (per cable)
Sensor Input Current
10 & micro;A ... 210 & micro;A (3-wire technology up to 2x 210 & micro;A)
Temperature measurement range
≥ 50 K