Phoenix MACX MCR-TC-I-temperature measurement transmitter 1050228, temperature measurement transmitter: convert thermocouple signal and mV source into 0/4... 20 mA signal. Freely programmable, 3-way galvanic isolation, screw connection, SIL.
| Product Type |
temperature measurement transmitter |
| product series |
MACX Analog |
| Application |
temperature |
| Channels |
1 |
| Model |
Isolation Amplifier with SIL Functional Safety |
| configuration |
Software |
| Function |
| configuration |
Software |
| electrical isolation |
3 End Isolation |
| Cold spot error, max |
± 2 K |
| step response (0-99%) |
≤ 1.7 s |
| temperature coefficient, typical |
0.01 %/K |
| Typical transmission error |
0.1 % (see data sheet for full transmission error recognition) |
| electrical isolation |
| Test Voltage |
2.5 kV AC (50 Hz, 60 s) |
| Overvoltage Category |
II |
| pollution level |
2 |
| Electrically isolated input/output/power supply IEC/EN 61010-1 |
| Standards/Regulations |
IEC/EN 61010-1 |
| Rated insulation voltage |
300Vrms |
| insulation |
security isolation |
| electrical isolation input/output IEC/EN 60079-11 |
| Standards/Regulations |
IEC/EN 60079-11 |
| Rated insulation voltage |
375VPP |
| galvanically isolated input/power supply IEC/EN 60079-11 |
| Standards/Regulations |
IEC/EN 60079-11 |
| Rated insulation voltage |
375VPP |
| power supply |
| Rated supply voltage |
24V DC -20 % ... +25% |
| Supply Voltage Range |
19.2V DC ... 30V DC |
| Maximum current consumption |
< 40 mA (24V DC) |
| power consumption |
≤ 0.76W |
| power consumption |
≤ 1W |
| signal |
| Input Number |
1 |
| input signal |
temperature |
| voltage |
| measurement |
| Available Sensor Types (TC) |
B, E, J, K, N, R, S, T, L, U, C, D, A- 1, A- 2, A- 3, M, Lr |
| Temperature measurement range |
-250°C ... 2500°C (range depends on sensor type) |
| sensor type: |
500°C ... 1820°C |
| -230°C ... 1000°C |
| -210°C ... 1200°C |
| -250°C ... 1372°C |
| -200°C ... 1300°C |
| -50°C ... 1768°C |
| -50°C ... 1768°C |
| -200°C ... 400°C |
| -200°C ... 900°C |
| -200°C ... 600°C |
| 0°C ... 2315°C |
| 0°C ... 2315°C |
| 0°C ... 2500°C |
| 0°C ... 1800°C |
| 0°C ... 1800°C |
| -200°C ... 100°C |
| -200°C ... 800°C |
| Linear mV Signal Range |
-1000 mV ... 1000 mV |
| Temperature measurement range |
Minimum 50 K with thermocouple, 10% of nominal range with mV supply |