Phoenix MACX MCR-T-UI-UP-SP-temperature measurement transmitter 2811860, freely programmable temperature measurement transmitter, with analog output and 1 threshold relay output, standard configuration, 2-, 3-or 4-wire resistance thermometer, thermocouple, galvanic isolation, wide-area power supply, plug-in interface, SIL,PL.
| Product Type |
temperature measurement transmitter |
| Product Series |
MACX Analog |
| Model |
isolation amplifier with SIL and PL functional safety |
| configuration |
DIP switch |
| Software |
| insulation characteristics |
| Overvoltage Category |
II |
| pollution level |
2 |
| Function |
| configuration |
DIP switch |
| Software |
| electrical isolation |
4 road isolation |
| rated conditions |
1.26W |
| step response (0-99%) |
≤ 1.75 s (SIL on) |
| 1.3 s (SIL off) |
| maximum temperature coefficient |
0.01 %/K |
| Maximum transmission error |
0.1 % (for example, when Pt 100,300 K minimum range) |
| Electrical isolation input/output/power supply |
| Rated insulation voltage |
300Vrms |
| Test Voltage |
2.5 kV AC (50 Hz, 60 s) |
| insulation |
safety isolation conforming to IEC/EN 61010-1 |
| electrically isolated input/output |
| electrical isolation |
375V (peak according to IEC/EN 60079-11) |
| Electrically isolated input/power supply |
| electrical isolation |
375V (peak according to IEC/EN 60079-11) |
| galvanically isolated input/switch output |
| electrical isolation |
375V (peak according to IEC/EN 60079-11) |
| Power |
| Rated supply voltage range |
24V AC/DC ... 230V AC/DC -20 % ... +10 % (50/60 Hz) |
| Supply Voltage Range |
19.2V AC/DC ... 253V AC/DC (50/60 Hz) |
| Typical current consumption |
< 50 mA (24V DC) |
| power consumption |
< 1.5W |
| signal |
| Input Number |
1 |
| input signal |
temperature |
| resistance |
| voltage |
| measurement |
| Available Sensor Types (RTDs) |
Pt, Ni, Cu sensors: 2, 3, 4 wires |
| Available Sensor Types (TC) |
B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG |
| Temperature measurement range |
-250°C ... 2500°C (range depends on sensor type) |
| Linear resistance measuring range |
0 Ω ... 50 kΩ |
| potentiometer, resistance range |
0 Ω ... 50 kΩ |
| Linear mV Signal Range |
-1000 mV ... 1000 mV |