Phoenix AXC F 2152-controller 2404267, used to directly control the PLCnext Control of Axioline F I/O. With two Ethernet interfaces. Includes connectors and bus base modules.
Product Type
controller
product series
PLCnext Control
type
Module
insulation characteristics
protection level
III (IEC 61140,EN 61140,VDE 0140-1)
Overvoltage Category
II
pollution level
2
Display
Diagnostic Display
No
Trusted Platform Module
TPM 1.2
Processor
Arm®Cortex®-A9, 2x 800 MHz
Flash
512 Mbyte (Internal Flash)
Phoenix Electric SD card (external flash memory please see attachment)
reserved data storage
48 kilobytes kByte (NVRAM)
RAM
512 Mbyte DDR3 SDRAM
IoT features: PROFICLOUD
IoT Platform
PROFICLOUD
support for cloud computing
is
IEC 61131 runtime system
Program Memory
8 Mbyte
data storage system
12 Mbyte
Axioline
Process Data Volume
Maximum 1482 Byte (per station (total input and output data))
up to 1024 Byte (Axioline F local bus (input))
max. 1024 Byte (Axioline F local bus (output))
maximum 63 (per station)
the number of local bus devices that can be connected
max. 63 (note current loss)
PROFINET
Device Features
PROFINET controller, PROFINET equipment
Update Rate
1 ms minimum (4 devices)
16 ms minimum (64 devices)
Conformance Class
B
max. 64 (in PROFINET controller)
Supported Features
MRP FSU PROFINET Controller
MRP PROFINET equipment
Device ID
0142hex
Vendor ID
00B0hex
Function
Diagnostic Display
No
redundancy function
is
Notes on redundant features
Application System Redundancy
safety function
No
Notes on safety features
provides functional safety through AXC F XT SPLC 1000 or AXC F XT SPLC 3000 expansion modules that can be installed side-by-side on the left.