Phoenix AXL E ETH IOL8 DI4 M12 6P-Communication module 2701536,Axioline E,Ethernet,M12 connector, IO-Link port type A: 4, connection mode: M12 connector, connection technology: 3 wires, IO-Link port type B: 4, connection mode: M12 connector, connection technology: 3 wires, digital input at 2 of A- level port pin plug: 4,24V DC, connection technology: 3-wire, plastic housing, protection class: IP65/IP67
| width |
60mm |
| height |
185mm |
| depth |
30.5mm |
| hole spacing |
198.5mm |
| Notes on dimensional data |
height is 212mm including the retaining clip. |
| Application Description |
| Application Description |
for industrial applications only |
| Use Restrictions |
| EMC Description |
EMC: Class A products, see the manufacturer's declaration in the download area |
| Shell Material |
Pocan® |
| color |
dark gray |
| Ethernet |
| interfaces |
2 |
| Connection Mode |
M12 Connector |
| Connection Method Considerations |
D coding |
| Bits |
4 |
| transmission speed |
10/100 MBit/s (adaptive) |
| Modbus/TCP |
| Device Type |
Modbus Slave (Server) |
| System Specific Protocol |
Modbus transmission protocol Modbus/TCP |
| Supported Protocols |
SNMP v1 |
| HTTP |
| TFTP |
| FTP |
| BootP |
| DHCP |
| Specification |
Modbus Application Transport Protocol V1.1b |
| digital quantity: |
| Enter Name |
Digital Input at Pin Plug 2 for Class A Port |
| Input Description |
IEC 61131-2 Type 1 |
| Input Quantity |
4 |
| Connection Mode |
M12 connector, X01. .. X04 with dual channel |
| connection system |
3 lines |
| input voltage range, "0" signal |
-0.3V DC ... 5V DC |
| input voltage range, "1" signal |
15V DC ... 30V DC |
| Rated input voltage UIN |
24V DC |
| Rated input current UIN |
Typical 3 mA |
| sensor current per channel |
Maximum 200 mA (off L /L-) |
| Total sensor current |
Maximum 1.6 A (off L /L-) |
| input frequency |
0.5 kHz |
| input filter time |
< 1000 µs |
| protection circuit |
overload protection, sensor power short circuit protection |