Phoenix AXL E IOL AI1 U M12 S-analog module 2700336,Axioline E IO-Link/analog converter, used to connect an analog sensor, 0V ... 10V,M12 connector, straight head model

Product Type Interface Interface Converter
Product Series Axioline E
type Stand-Alone
Axioline E
Model Straight
diagnostic information Overflow or Underflow Diagnostic Coding Information (IB IL Format)
invalid measured value/no valid measured value diagnostic code message (IB IL format)
module error diagnosis coding information (IB IL format)
insulation characteristics
pollution level 2

power supply: IO-Link
I/O power supply 24V DC (Power is supplied through the IO-Link interface of the IO-Link master station.)
current rating for each IO-Link port Max. 100 mA
power consumption Typical 16.5 mA ± 15% (24V DC)
Max. 120 mA
protection circuit polarity protection
short circuit protection
overload protection

simulation: overview
Enter Name Analog Input
Input Quantity 1 (voltage)
A/D Converter Resolution 12.
Connection Mode M12 connector, A- code
connection system 3 lines
voltage input signal 0V ... 10V
input voltage minimum 100 kΩ
data format IB IL,S7 Compatible
filtering none or main value
IO-Link
ports 1
Connection Mode M12 connector, A- code
connection system 3 lines
Specification V1.1.1
prevents polarity reversal is
cycle minimum 2 ms
Process Data Volume 16 bits (input data)
16 bits (output data)

Diagnostic Messages
diagnosis overflow or underflow
Message diagnostic coded information (IB IL format)
Diagnostic Messages
diagnosis invalid measured value/no valid measured value
Message diagnostic coded information (IB IL format)
Diagnostic Messages
diagnosis Module Error
Message diagnostic coded information (IB IL format)
2700338

Phoenix AXL E IOL AI1 U M12 S-Analog Module 2700336

Product Center

PRODUCT CENTER